Features:
- Scales the S-to-C voltage command for SCR firing control.
- Shifts firing-pulse timing in nonreversing exciter operation.
- Coordinates forward and reverse firing paths through reversing logic.
IC3600TCBA1 sits between the external exciter command and the low-level firing circuits rather than in the thyristor load path.
Command polarity at IC3600TCBA1 determines the requested output direction when the exciter includes reversing logic.
The scaled signal from IC3600TCBA1 changes firing phase while the gate-and-filter circuits deliver the actual pulses to the SCR cells.
The General Electric IC3600TCBA1 SCR Exciter Comparator Card may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IC3600TCBA1 SCR Exciter Comparator Card Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Command Path
- Input pair: IC3600TCBA1 receives the exciter demand between S and C.
- Scaling: The CB path reduces the command to the level required by the firing circuits.
- Boundary: The card processes a low-level control signal rather than exciter load current.
Pulse Timing
- Initial state: At zero command, gate pulses occur while the addressed SCR is reverse biased.
- Command effect: A larger negative S command advances the effective firing interval.
- Result: IC3600TCBA1 moves the pulses into the forward-conduction portion of the cycle.
Direction Logic
- Positive output: Negative S selects the forward F1F path.
- Negative output: Positive S is inverted for the R1F path in a reversing exciter.
- Interlock: The opposite direction remains locked until the conducting thyristors turn off.
Circuit Boundary
- Comparator role: IC3600TCBA1 scales and routes the exciter command.
- Pulse delivery: Gate-and-filter circuits carry the firing pulses to the SCR cells.
- Power stage: The SCR bridge converts AC input power to controlled DC output.