Features:
- Twenty-four dry-contact channels enter through pluggable H2 termination.
- The terminal assembly is dedicated to nominal 24 V DC excitation.
- Optical conversion separates field contact states from pack logic.
IS230SNCIH2A divides its input load between a 21-circuit group and three higher-current positions.
Hardware filtering precedes the PDIAH1B contact-state logic, limiting short disturbances before controller transfer.
Excitation supervision and electronic identification distinguish a supply loss from incompatible terminal hardware.
The General Electric IS230SNCIH2A EX2100e Mark VIe 24 V DC Digital Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IS230SNCIH2A EX2100e Mark VIe 24 V DC Digital Input Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Channel Organization
- Total inputs: Twenty-four dry-contact circuits are provided.
- Inputs 1–21: Each channel draws 2.5 mA.
- Inputs 22–24: Each of the final three draws 10 mA.
- Common structure: The channels share the floating excitation arrangement.
Contact Supply
- Nominal level: The H2 group is designed for 24 V DC excitation.
- Working range: The accepted supply span is 18.5–32 V DC.
- Normal threshold: Contact switching is set at 50% of excitation.
- Low supply: Under-voltage detection operates below 40%.
Input Conversion
- Isolation stage: Optocouplers transfer the contact state to logic.
- Filter time: The hardware input filter is 4 ms.
- AC rejection: The 24 V group rejects 12 V rms.
- Channel relation: Inputs are not isolated from one another.
Input Supervision
- Supply loss: Missing contact excitation creates an input-board fault.
- Test response: A nonresponding contact is identified during test mode.
- Board match: An ID mismatch reports incompatible terminal hardware.