Features:
- Twelve form-C relays provide the base field-output paths.
- An isolated contact pair returns each relay position.
- JW1 and JW2 accept supported relay option hardware.
IS230SNRLH2A applies different current limits to its DC and AC load-voltage groups.
The SRLYH2A field section remains simplex even though the PDOAH1B pack can communicate over two networks.
Command comparison, contact feedback, and electronic identification supervise the output assembly without base-board jumpers.
The General Electric IS230SNRLH2A EX2100e Mark VIe Relay Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IS230SNRLH2A EX2100e Mark VIe Relay Output Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Contact Layout
- Relay count: Twelve form-C channels are fitted.
- Field access: Customer circuits use 48 pluggable terminals.
- Topology: SRLYH2A is a simplex S-type board.
- Contact material: Relay contacts use silver cadmium oxide.
Resistive Ratings
- 24 V DC: Maximum load current is 3.15 A.
- 48 V DC: Maximum load current is 1.2 A.
- 125 V DC: Maximum load current is 0.6 A.
- AC circuits: 120/240 V AC loads are rated to 3.15 A.
Auxiliary Relay Boards
- Connectors: JW1 and JW2 carry option-board connections.
- Supported hardware: WROB, WROF, and WROG boards are listed.
- Base assembly: SOL terminals are open without an option board.
- Settings boundary: Option fuses or jumpers are separate from SRLY setup.
Output Supervision
- Position return: An isolated pair reports relay contact state.
- Command check: The pack compares drive and returned position.
- Identity test: Board-type mismatch produces a diagnostic.
- Base setup: SRLY itself contains no configuration jumpers.