Features:
- Monitors six thermocouple inputs in three isolated groups while accepting AC or DC block power.
- Handles J, K, T, E, B, R, S, and N sensors plus -25 to +150 mV signals.
- Provides internal, remote, or configured cold-junction compensation with channel diagnostics.
Internal compensation can be adjusted at the operating temperature, while external XJV and XJI inputs scale junction temperature in voltage or current form.
The complete channel set updates in 2 seconds typical, and open-wire detection responds in less than 5 seconds.
IC660BBA103 uses 9 W maximum from 93-132 VAC or 105-145 VDC and maintains 300 V isolation between input groups.
Availability may continue through Apter Power for the General Electric IC660BBA103 115 VAC/125 VDC Thermocouple 6 Input Block after the manufacturer reaches End-of-Life.
General Electric IC660BBA103 115 VAC/125 VDC Thermocouple 6 Input Block Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC660BBA103 115 VAC/125 VDC Thermocouple 6 Input Block Specs
General
- ManufacturerGeneral Electric
- ModelIC660BBA103
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Cold-Junction Options
- Internal Sensor: Uses the block cold-junction sensor.
- External Voltage: Accepts 1.0 mV per degree Celsius.
- External Current: Accepts 1.0 µA per kelvin.
- Configured Value: Allows a user-defined compensation value.
- Adjustment: Supports channel correction up to ±100°C or ±100°F.
Temperature and Millivolt Inputs
- Thermocouples: Supports J, K, T, E, B, R, S, and N types.
- Millivolts: Measures signals from -25.0 to +150 mV.
- Linearization: Applies the selected thermocouple characteristic.
- Isolation: Separates the three input groups by 300 V.
Thermocouple Fault Indication
- Open Wire: Detects an open sensor circuit in under 5 seconds.
- Range Status: Reports overrange and underrange values.
- Alarm Limits: Provides high and low input alarms.
- Internal Fault: Reports internal block failures.
- Status Data: Sends measurements and diagnostic states over the Genius bus.