Features:
- Sixteen normally-closed relay outputs are arranged in four isolated groups
- Each relay circuit switches AC or DC loads up to the documented ratings
- Separate field sources may be used for the four output groups
IC660BBR100 identifies the normally-closed member of the sixteen-circuit Genius relay output pair; BBR101 is the separate normally-open configuration.
Mechanical relay contacts provide galvanic grouping and allow AC or DC field loads to be switched without sharing one source across all sixteen points.
Before replacement, compare contact form, load voltage, inrush, power factor, group wiring, suppression components, and the process response to de-energized relays.
The General Electric IC660BBR100 115/230 VAC 16-Circuit Normally-Closed Relay Block is available for quotation, official documentation, configuration review, and system-matching support from Apter Power.
General Electric IC660BBR100 115/230 VAC 16-Circuit Normally-Closed Relay Block Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC660BBR100 115/230 VAC 16-Circuit Normally-Closed Relay Block Specs
General
- ManufacturerGeneral Electric
- ModelIC660BBR100
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Four isolated banks
- Group structure: Four relays share each isolated output bank.
- Separate sources: Each bank may use its own compatible AC or DC supply.
- Contact state: The catalog configuration uses normally-closed contacts.
- Isolation: Preserve separation between groups and chassis wiring.
Contact application
- Voltage range: Apply loads from 5 to 250 VAC or 5 to 220 VDC.
- Current limit: Keep every relay circuit at or below 2 A.
- Switching power: Do not exceed 125 VA or 60 W at the contact.
- Minimum load: Observe the recommended current for reliable contact operation.
Relay service
- Turn-on time: Allow for the documented 5 ms maximum contact response.
- Inductive duty: Limit operating frequency for coils and other inductive loads.
- Suppression: Select load suppression without bypassing the required safe state.
- Wear review: Inspect application duty when replacing a high-cycle relay block.