P0904BS P0904BS-0E

/ 4.9
1001 reviews | Need a Specific Revision?
Foxboro P0904BS Rev 0E is an embedded GCIO interface module without touchscreen for supported I/A Series H92 workstation consoles.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for P0904BS P0904BS-0E
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for P0904BS P0904BS-0E

  • Manufacturer:
    Invensys
  • Part Number:
    P0904BS P0904BS-0E
  • Product Family:
    Foxboro
  • Product Type:
    I/A Series Embedded GCIO Interface Module without Touchscreen
  • Stock:
    1
  • Product role:
    Embedded GCIO workstation-peripheral interface
  • Console mounting:
    MIC, MIW or Command Center embedded installation
  • Touchscreen controller:
    Not included
  • Keyboard capacity:
    Up to two GCIO keyboards per module
  • Observed revision:
    REV 0E
  • Nameplate description:
    GCIO MIW W/O TS WP50
  • Weight:
    2.74 kg
  • Estimated shipping dimensions:
    4.3 x 20 x 40.5 cm
  • Tariff Code:
    Please confirm the destination before shipping
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Workstation Integration Peripheral Connections Revision & Identity Applications

Features:

  • Console interface: Embedded GCIO module for supported Foxboro I/A Series H92 workstation hardware.
  • No-touchscreen version: The nameplate identifies the supplied unit as GCIO MIW W/O TS WP50.
  • Keyboard capacity: One module connects as many as two supported GCIO keyboards.
P0904BS provides the graphics-controller input/output link between the configured workstation port and operator keyboards.

Its embedded MIC, MIW or Command Center format differs from the separately documented table-top GCIO arrangement.

When three or four supported GCIO keyboards are required, the H92 architecture adds a second module and the specified interconnect cabling.

Apter Power provides documentation, quotation and procurement support for the Invensys P0904BS P0904BS-0E I/A Series Embedded GCIO Interface Module without Touchscreen.
Invensys P0904BS P0904BS-0E I/A Series Embedded GCIO Interface Module without Touchscreen Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Supported host: Listed by Foxboro for the Model H92 workstation.
  • System Definition: The GCIO connects to the workstation serial port assigned in the system configuration.
  • Embedded console: Used within MIC, MIW or Command Center assemblies.
  • Replacement check: Match workstation generation, console mounting and the configured GCIO port.
  • Keyboard capacity: One module services up to two supported GCIO keyboards.
  • Expanded capacity: Three or four keyboards require a second GCIO module.
  • Workstation cables: P0971SU, P0971SV and P0971WZ cover 3 m, 15 m and 30 m runs.
  • Dual-GCIO arrangement: Foxboro also shows P0970HV and P0800MW interconnect cables.
  • Base model: P0904BS defines the embedded no-touchscreen GCIO function.
  • Revision: REV 0E identifies the observed hardware revision.
  • Search form: P0904BS-0E is retained for revision-aware sourcing, not treated as a different function.
  • RFQ practice: Quote the base model, revision and full nameplate wording together.
  • Operator interface: Connects supported annunciator-keyboard peripherals to an H92 workstation.
  • No touchscreen: Use a different supported GCIO variant when touchscreen control is required.
  • Not field I/O: It is not a PLC output card or process I/O module.
  • Service boundary: Match console mounting, port definition, keyboard type and cabling before release.
Description
P0904BS is the embedded Graphics Controller Input/Output interface used inside supported Foxboro I/A Series MIC, MIW and Command Center workstation hardware. The nameplate identifies this unit as the no-touchscreen WP50 version.

A single module connects the workstation's configured GCIO port to as many as two annunciator or annunciator/numeric keyboards. Systems with three or four GCIO keyboards require a second module and the documented interconnect cabling.

REV 0E identifies the supplied hardware revision; P0904BS-0E is retained as a searchable revision form, not a different base function. Replacement review should match the embedded mounting, workstation generation, port definition, keyboard type, cable set and complete nameplate.
Alternative Names
P0904BS P0904BS-0E P0904BS 0E P0904BS REV 0E Foxboro P0904BS Invensys P0904BS
Technical notes
P0904BS is the embedded no-touchscreen GCIO for supported H92 console hardware. P0904AK is a table-top version and is not established as a direct mechanical replacement. Three or four GCIO keyboards require a second module and the documented cable arrangement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can P0904BS/P0904BS-0E directly replace P0904AK in an H92 console?
No. Foxboro identifies P0904BS as the embedded no-touchscreen GCIO and P0904AK as the table-top version, so mounting and console architecture must be checked before substitution.
How many keyboards can one P0904BS/P0904BS-0E support?
One module services up to two supported GCIO annunciator or annunciator/numeric keyboards. A third or fourth keyboard requires a second GCIO and the documented interconnect arrangement.
Which workstation-to-GCIO cables are documented for P0904BS/P0904BS-0E?
Foxboro lists P0971SU at 3 m, P0971SV at 15 m and P0971WZ at 30 m. Confirm the existing route and connector plan before ordering.
Is P0904BS/P0904BS-0E suitable when the operator station needs a touchscreen?
No. The nameplate and H92 documentation identify this as the no-touchscreen GCIO. Select the workstation-supported touchscreen GCIO variant instead.
Should an RFQ list P0904BS/P0904BS-0E or only the base number?
List P0904BS and the observed REV 0E together. Keeping the revision prevents a supplier from treating a physically different revision as an exact match without review.
What should be checked when P0904BS/P0904BS-0E is installed but the keyboard does not respond?
Verify the H92 System Definition port, workstation-to-GCIO cable, keyboard type and address, and any second-module interconnect before treating the fault as field I/O.