Features:
- Acquires thirty-two differential, DC-coupled input points across a 0–10 V range.
- Uses triple modular redundant channels and mid-value selection for each scan.
- Provides 12-bit resolution with a documented 55 ms input update rate.
The selected configuration is the 0–10 V member of the classic thirty-two-point differential analog-input group.
It brings process voltage signals into the TMR controller while maintaining independent conversion and diagnostics on all three channels.
Engineering review should cover field references, shunt values, overrange protection, termination hardware and chassis keying.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Triconex 3701:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Collects differential voltage measurements from process transducers in safety and critical-control systems.
- Accepts 0–20 mA loops through the documented 500-ohm shunt arrangement.
- Supports online maintenance strategies through the analog-input hot-spare architecture.
- A 55 ms input update rate supports repeated acquisition across all thirty-two differential channels.
- Twelve-bit conversion provides the documented measurement resolution for the 0–10 VDC range.
- Accuracy remains below 0.15% of full scale across the specified 0°C to 60°C interval.
- Three independent input channels allow the main processors to select the mid-value from triplicated data.
- Continuous diagnostics identify a failed acquisition path while healthy paths continue to report measurements.
- Input circuitry provides continuous overrange protection up to the documented 150 VDC or 115 VAC limit.
- Thirty-two differential, DC-coupled points acquire 0–10 VDC process measurements.
- A 500-ohm shunt converts a supported 0–20 mA loop into the module voltage range.
- Pass, Fault and Active indicators provide local status for maintenance observation.