Features:
- One 10/100 Ethernet port for application and diagnostics
- Ten Modbus TCP/IP client connections
- Ten Modbus TCP/IP server connections
MVI69L-MBTCP is the Lite CompactLogix option for smaller systems that need Modbus TCP/IP client and server communication in a 1769 slot.
Ten client connections can execute as many as 16 configured commands each, while ten server connections expose the mapped module data to remote clients.
Check the CompactLogix processor, firmware, 1769 power distance, Ethernet addressing, polling schedule, and 240-word controller transfer before installation.
The ProSoft MVI69L-MBTCP Modbus TCP/IP Lite Communication Module for CompactLogix is listed as Active / Available from OEM. Apter Power supports CompactLogix matching and quotation requests.
ProSoft MVI69L-MBTCP Modbus TCP/IP Lite Communication Module for CompactLogix Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ProSoft MVI69L-MBTCP Modbus TCP/IP Lite Communication Module for CompactLogix Specs
General
- ManufacturerProSoft Technology
- ModelMVI69L-MBTCP
- ConditionNew Original ready stock
- Product FamilyCompactLogix Communication Module
Lite client and server limits
- Client connections: MVI69L-MBTCP supports a maximum of 10 Modbus TCP/IP clients.
- Commands per client: Each client connection can contain up to 16 configurable commands.
- Server connections: The module provides 10 Modbus TCP/IP server connections.
- Polling choices: Commands can poll continuously, on data change, dynamically, or under automatic control.
Controller integration details
- Target platform: The module is intended for smaller CompactLogix applications using the 1769 I/O bus.
- Data transfer: The controller I/O image contains 240 16-bit words.
- Backplane demand: Maximum current load is 450 mA at 5 VDC.
- Project integration: The Add-On Profile and Add-On Instruction organize configuration, status, and application tags.
Ethernet commissioning
- Shared port: One 10/100 RJ45 port carries Modbus TCP/IP application traffic and diagnostic access.
- Addressing: Assign the module IP parameters and confirm every client target and server route.
- Error visibility: Per-command errors, client status, counters, and server status support troubleshooting.
- Application check: MicroLogix 1500 is not supported; verify processor and 1769 bus compatibility before ordering.