Features:
- CPU 313C processing and 128 KB work memory support compact S7-300 machine-control programs.
- Integrated digital, analog, and Pt100 channels reduce the need for separate signal modules.
- Three 30 kHz counters handle pulse and frequency tasks close to the controller.
Siemens 6ES7313-5BG04-0AB0 combines an S7-300 CPU, onboard I/O, and technology functions in a single compact control module.
The 24 digital inputs, 16 digital outputs, analog channels, Pt100 measurement, and fast counters support mixed machine signals without expanding every function into a separate module.
An MPI interface, SIMATIC Micro Memory Card, and two 40-pin front connectors complete the engineering and wiring structure that must be checked during commissioning or replacement.
The Siemens 6ES7313-5BG04-0AB0 SIMATIC S7-300 CPU 313C Compact Central Processing Unit may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7313-5BG04-0AB0 SIMATIC S7-300 CPU 313C Compact Central Processing Unit Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Onboard Signal Channels
- Digital inputs: Twenty-four integrated channels receive discrete machine states.
- Digital outputs: Sixteen integrated channels drive configured control loads.
- Analog channels: Four analog inputs and two analog outputs handle continuous signals.
- Temperature input: One Pt100 channel supports resistance-temperature measurement.
Integrated Technology Functions
- Counter channels: Three onboard counters process signals up to 30 kHz.
- Frequency tasks: Counter resources can be parameterized for frequency measurement.
- Pulse functions: Integrated outputs support configured pulse-generation tasks.
- Channel planning: Terminal assignments and technology parameters must match the STEP 7 hardware configuration.
Program Storage and Communication
- Work memory: The CPU provides 128 KB for program execution and runtime data.
- Load memory: A SIMATIC Micro Memory Card is required for the controller project.
- MPI network: The integrated MPI interface supports programming and configured S7 communication.
- Replacement control: Project, MMC, hardware version, and I/O parameters should be verified before changeover.
Connector and Commissioning Checks
- Front connectors: Two 40-pin connectors are needed to terminate the integrated I/O.
- Supply: The controller operates from a 24 V DC supply within the specified tolerance.
- Hardware setup: Rack position, grounding, connector coding, and channel assignments must agree with the project.
- First start: Load the verified MMC project, check diagnostics, and test outputs under safe machine conditions.