Features:
- 6ES7323-1BH01-0AA0 combines eight digital inputs and eight digital outputs.
- The 24 V DC field circuits are isolated from the S7-300 backplane.
- Green channel LEDs expose input and output states without a diagnostic alarm channel.
The 6ES7323-1BH01-0AA0 condenses the sensing and switching sides of an SM 323 into one slot.
A common L+ field supply serves the module while optocouplers separate its I/O groups from the backplane logic.
The 20-pin connector, eight-output group limit and existing wire assignments must agree during module matching.
The Siemens 6ES7323-1BH01-0AA0 SM 323 Isolated Digital I/O Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7323-1BH01-0AA0 SM 323 Isolated Digital I/O Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
How field voltage becomes an S7-300 logic state
- Low state: Voltages from -30 to +5 V are interpreted as signal 0.
- High state: The signal-1 window begins at 13 V and extends to 30 V.
- Input current: A high input draws approximately 7 mA.
- Transfer delay: Both transition directions pass through a 1.2–4.8 ms delay.
Relating each channel to the shared load boundary
- Channel rating: Each output carries a 0.5 A rated signal-1 current.
- Group total: The eight outputs share a 4 A maximum-current boundary.
- Protection response: Electronic short-circuit protection responds at approximately 1 A.
- Redundant drive: Two outputs may control one load redundantly only when they belong to the same group.
Separation between field circuits and the backplane
- Input boundary: The input group is optically isolated from the S7-300 backplane.
- Output boundary: The output group uses a separate optocoupler path to the backplane.
- Test level: Isolation is tested at 500 V DC.
- Field commonality: Channels remain organized in groups of eight rather than as individually isolated points.
Checks at the removable field interface
- Connector format: The module requires a 20-pin S7-300 front connector.
- Supply placement: The L+ range is 20.4–28.8 V DC before field loads are considered.
- Cable reach: Documented limits are 1,000 m shielded and 600 m unshielded.
- LED use: Green indicators confirm channel state but do not replace electrical checks because diagnostics are absent.