Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power supports quotation, cutout review, official documentation, and coordinated sourcing.

2711P-T6C21D8S

/ 4.9
1001 reviews | Need a Specific Revision?
Compact 5.7-inch PanelView Plus 7 Standard touch terminal with one Ethernet port for endpoint HMI installations.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for 2711P-T6C21D8S
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 2711P-T6C21D8S

  • Manufacturer:
    Allen-Bradley
  • Part Number:
    2711P-T6C21D8S
  • Product Family:
    Panelview Plus
  • Product Type:
    PanelView Plus 7 Standard Graphic Terminal
  • Stock:
    1
  • Display Size:
    5.7 in.
  • Operator Input:
    Resistive touch
  • Display Type:
    Color TFT LCD
  • Resolution:
    640 × 480 VGA
  • Aspect Ratio:
    4:3
  • Input Voltage:
    24 V DC
  • Communication:
    One 10/100 Ethernet port with IEEE 1588 support
  • Operating System:
    Windows CE 6
  • Weight:
    0.7 kg
  • Estimated shipping dimensions:
    15.2 × 17.6 × 5.65 cm
  • Tariff Code:
    8537101190
  • Country of origin:
    Japan
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Fit Star Files Product Applications

Features:

  • Small panel footprint: 5.7-inch VGA touch hardware
  • Endpoint network: one Ethernet port for star wiring
  • Lower power class: 35 W maximum at the documented DC input range

The 21 network code makes this compact terminal a single-cable endpoint rather than a ring participant.

Its panel outline and mounting template differ from larger Standard terminals even when the project uses the same 4:3 aspect ratio.

A successful retrofit preserves both physical fit and the application, addressing, Series, and firmware record.

For 2711P-T6C21D8S, Apter Power can coordinate official-data verification, quotation, and sourcing assistance.

Verified resources for 2711P-T6C21D8S:

Important Notice: Confirm the required firmware, application files, cables, accessories, and documentation in the quotation before ordering.
  • Correct outline: use the 152 by 176 mm terminal body and official cutout template.
  • Gasket contact: keep the panel flat, clean, and within the documented thickness.
  • Lever positions: engage every required mounting slot for the 5.7-inch hardware.
  • Stop condition: do not enlarge or reuse an opening until edge distance and enclosure integrity are confirmed.
  • One port: connect the terminal as a single endpoint to an Ethernet switch.
  • No pass-through: provide another network path if the removed HMI carried downstream traffic.
  • Address record: preserve the approved IP, subnet, gateway, device name, and controller shortcut.
  • Commissioning: prove tag reads and a controlled command after the cable is restored.
  • Application files: retain the ME runtime and communication configuration before removal.
  • SD storage: use supported 1784-SDx media for external files.
  • USB transfer: keep service devices within the official installation and hazardous-area rules.
  • Restore gate: match the backup to the target Series firmware before loading.
  • Compact machine panels: provide local touch visualization where cabinet space is limited.
  • Star-connected Logix HMI: monitor and control one supported controller through a single Ethernet link.
  • VGA ME applications: run up to the documented Standard screen and alarm limits on a 4:3 display.
Description

Space-limited machine panels use 2711P-T6C21D8S as a compact 5.7-inch VGA touch endpoint with one Ethernet connection and 24 V DC input.


Because 2711P-T6C21D8S has the 21 single-port network code, it connects through a star switch and cannot continue a DLR or in-line Ethernet path.


The installed cutout, FactoryTalk View ME runtime, controller shortcut, application backup, hardware Series, and power wiring should all be recorded before 2711P-T6C21D8S is exchanged.

Revisions

Revision Part #

Also known as

2711P-T6C21D8S Series A
2711P-T6C21D8S/A, Series A
2711P-T6C21D8S Series C
2711P-T6C21D8S/C, Series C
2711P-T6C21D8S Series D
2711P-T6C21D8S/D, Series D
Alternative Names
Allen-Bradley 2711P-T6C21D8S AB 2711P-T6C21D8S 2711P T6C21D8S 2711PT6C21D8S 2711P-T6C21D8S compact PanelView PanelView Plus 7 5.7-inch single-port HMI
Technical notes
Use the official 5.7-inch cutout for 2711P-T6C21D8S; its terminal body is 152 by 176 mm, not the wider legacy value sometimes copied from neighboring displays. Compare the existing opening and lever locations to the current template, and stop fabrication if the old panel cannot retain the required gasket and mounting engagement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why can 2711P-T6C21D8S not replace a dual-Ethernet HMI without a topology change?
The 21 catalog position provides one Ethernet port, so it cannot maintain DLR or linear pass-through wiring. Provide a star-switch connection or select the documented dual-port variant before removing the old terminal.
What should an installer do when the old panel opening does not match 2711P-T6C21D8S?
Compare the opening with the official 5.7-inch cutout and verify gasket coverage, edge distance, and mounting-lever engagement. Stop cutting if the enclosure rating or door strength would be compromised.
How can the DC supply be accepted for 2711P-T6C21D8S during retrofit?
Measure 18...30 V DC at the terminal under startup load and allow for its 35 W maximum demand. Correct voltage drop, wiring, or source capacity before loading the application.
Why can a larger-terminal project require redesign before loading into 2711P-T6C21D8S?
This target uses a 640 × 480 4:3 workspace and Standard-model capacity limits. Rebuild navigation and touch targets for the smaller view, then validate every operator task on the actual terminal.
How should a saved application be restored to 2711P-T6C21D8S from removable media?
Confirm the hardware Series, supported firmware, and ME runtime version first. Copy the approved files through the supported SD or USB workflow, restore communication settings, and test the controller shortcut before production.
Which records should accompany a 2711P-T6C21D8S sourcing request?
Provide the exact 21 single-port code, hardware Series, firmware, application backup, current cutout measurement, label photos, quantity, destination, and required delivery date.