IC697CMM741
IC697CMM741
IC697CMM741
IC697CMM741
IC697CMM741
IC697CMM741
Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
How We Verify Your Order
Before dispatch, we confirm the exact model, revision, condition, inspection requirements and shipping documents for your order.
See a real on-site verification case >>
  • Lifecycle status

    Retired

IC697CMM741

/ 4.9
1001 reviews | Need a Specific Revision?
GE IC697CMM741 attaches a Series 90-70 PLC to a 10 Mbps IEEE 802.3 network through an external AUI transceiver.
In Stock
Ships by Saturday, November 14
Fast Shipping Available
Get a quick price for IC697CMM741
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for IC697CMM741

  • Manufacturer:
    General Electric
  • Part Number:
    IC697CMM741
  • Product Family:
    GE 90-70 Series PLC
  • Product Type:
    Type 1 Ethernet Controller Module
  • Stock:
    1
  • Network Standard:
    IEEE 802.3 CSMA/CD
  • Network Rate:
    10 Mbps
  • Network Connector:
    15-pin female AUI
  • Supported Media:
    10Base5, 10Base2, 10BaseT, 10BaseF, 10Broad36 via transceiver
  • Local Port:
    9-pin female RS-232 DTE
  • Local Port Rate:
    9,600 bps
  • 5 V Demand:
    1.0 A
  • 12 V Demand:
    0.5 A
  • Retention:
    At least 6 months with on-board battery
  • Slot Use:
    Single slot
  • Installation:
    First available slot right of CPU or BTM; no empty slot to left
  • Dimensions:
    3.8 × 29.2 × 22.9 cm
  • Weight:
    0.4 kg
  • Tariff Code:
    8538900000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Network Migration Rack Placement Recovery Plan Application
  • Legacy Series 90-70 Ethernet controller with a 15-pin AUI network interface
  • Requires a compatible external transceiver for the selected IEEE 802.3 medium
  • Software, station configuration, battery retention and rack placement must be preserved

IC697CMM741 provides the Ethernet LAN processor used by legacy Series 90-70 programming, PLC communication and station-management services.

The network connection uses a 15-pin AUI interface and a user-supplied transceiver rather than a direct RJ45 port; the selected TCP/IP or MMS/OSI software is loaded into battery-backed RAM.

Replacement planning must confirm the hardware revision, installed software package, external transceiver, 9-pin local station-manager connection, battery condition and the required rack position.

Availability, condition, price, and shipping time for IC697CMM741 are confirmed during quotation.

GE IC697CMM741 Type 1 Ethernet Controller Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Record the loaded TCP/IP or MMS/OSI package
  • Capture station parameters and peer addresses
  • Identify the AUI transceiver and physical medium
  • Use the first available slot right of CPU or BTM
  • Do not leave an empty slot to the module's left
  • Confirm both +5 V and +12 V supply capacity
  • Retain software media and configuration backups
  • Replace or verify the lithium battery before extended outage
  • Test station-manager and PLC network services
  • Legacy Series 90-70 PLC Ethernet programming
  • TCP/IP PLC communication through an AUI transceiver
  • MMS/OSI Factory LAN integration
Description
IC697CMM741 occupies one Series 90-70 slot and provides the LAN processor used by legacy programming, station-management and PLC communication services.

Its software is loaded into RAM and retained by the on-board lithium battery during rack power loss. The selected TCP/IP or MMS/OSI package and station configuration therefore belong to the replacement plan.

The module requires both +5 V and +12 V rack power, must have no empty slot to its left, and uses a 9-pin RS-232 port for the Local GSM plus a 15-pin AUI connector for the transceiver.
Revisions

Revision Part #

Also known as

IC697CMM741H
IC697CMM741-H, Series H, Rev H
IC697CMM741L
IC697CMM741-L, Series L, Rev L
IC697CMM741M
IC697CMM741-M, Series M, Rev M
Alternative Names
IC 697 CMM 741 GE Fanuc IC697CMM741 GE IC697CMM741 General Electric IC 697 CMM 741 General Electric IC697CMM741
Technical notes
IC697CMM741 requires its licensed network software, station parameters, healthy backup battery, +5 V and +12 V capacity, adjacent-slot placement, AUI transceiver, and cable medium to be preserved.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What must accompany GE IC697CMM741 for a copper 10BaseT connection?
A compatible external AUI transceiver and transceiver cable are required; the module itself does not provide a direct RJ45 port.
What configuration must be recovered before replacing GE IC697CMM741?
Record the loaded TCP/IP or MMS/OSI package, IP and station parameters, network medium, transceiver, local GSM settings and PLC project dependencies.
Why can GE IC697CMM741 lose its network software after a long outage?
The software resides in RAM and depends on the on-board battery during power loss. Check battery condition and retain a verified reload package before the maintenance window.
Can GE IC697CMM741 be installed with an empty rack slot to its left?
No. The documented installation requires the first available slot to the right of the CPU or BTM, without empty slots to the module's left.
Why must the rack supply be checked for GE IC697CMM741?
The controller consumes both +5 V and +12 V, including allowance for external RS-232 loads and the transceiver; some rack supplies do not provide the required +12 V capacity.
How should GE IC697CMM741 be diagnosed when ONLINE remains off?
Check the AUI latch, external transceiver power and SQE setting, cable plant, loaded software, station parameters, battery-backed RAM and MODULE OK or STATUS OK indications.
What should be included in an operational test of GE IC697CMM741?
Verify PLC programming access, peer or host communication, station-manager diagnostics, recovery after a controlled power cycle and the expected battery-backed software retention.