- Legacy Series 90-70 Ethernet controller with a 15-pin AUI network interface
- Requires a compatible external transceiver for the selected IEEE 802.3 medium
- Software, station configuration, battery retention and rack placement must be preserved
IC697CMM741 provides the Ethernet LAN processor used by legacy Series 90-70 programming, PLC communication and station-management services.
The network connection uses a 15-pin AUI interface and a user-supplied transceiver rather than a direct RJ45 port; the selected TCP/IP or MMS/OSI software is loaded into battery-backed RAM.
Replacement planning must confirm the hardware revision, installed software package, external transceiver, 9-pin local station-manager connection, battery condition and the required rack position.
Availability, condition, price, and shipping time for IC697CMM741 are confirmed during quotation.
GE IC697CMM741 Type 1 Ethernet Controller Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Record the loaded TCP/IP or MMS/OSI package
- Capture station parameters and peer addresses
- Identify the AUI transceiver and physical medium
- Use the first available slot right of CPU or BTM
- Do not leave an empty slot to the module's left
- Confirm both +5 V and +12 V supply capacity
- Retain software media and configuration backups
- Replace or verify the lithium battery before extended outage
- Test station-manager and PLC network services
- Legacy Series 90-70 PLC Ethernet programming
- TCP/IP PLC communication through an AUI transceiver
- MMS/OSI Factory LAN integration