Features:
- Configures each of sixteen source-type circuits independently as an input, tristate input, or output.
- Operates from 18-56 VDC and supplies up to 2 A per output circuit with a 15 A block limit.
- Combines electronic output protection with open-wire, overload, no-load, and temperature diagnostics.
Source outputs can connect directly to compatible input circuits without external logic inversion or additional interface components.
A tristate input uses a 5.1 kΩ external resistor near the dry contact so the block can distinguish an open wire from a normal off state.
Input processing is 1.7 ms typical before the selectable 5-100 ms filter delay, while output turn-on is 1 ms maximum.
The General Electric IC660BBD020 24/48 VDC 16 Circuit Source I/O Block may still be supplied by Apter Power for installed systems beyond manufacturer EOL.
General Electric IC660BBD020 24/48 VDC 16 Circuit Source I/O Block Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC660BBD020 24/48 VDC 16 Circuit Source I/O Block Specs
General
- ManufacturerGeneral Electric
- ModelIC660BBD020
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Configurable Discrete Points
- Input: Reads a standard source-type field input.
- Tristate Input: Enables open-wire supervision with a 5.1 kΩ resistor.
- Output: Drives a DC load at up to 2 A per circuit.
- Direct Linking: Outputs may connect to inputs without logic inversion.
Source Output Performance
- Steady Current: Supports 2 A on each output circuit.
- Inrush: Handles 10 A for up to 10 ms.
- Block Limit: Combined output current is limited to 15 A at 35°C.
- Protection: Electronic protection turns off an overloaded output.
- Restoration: A controller or hand-held monitor command restores the circuit.
Discrete Circuit Protection
- Open Wire: Available for configured tristate inputs.
- Overload: Detects excessive output current and shuts down the point.
- No Load: Identifies an output without its expected load.
- Failed Switch: Reports output switching faults.
- Overtemperature: Monitors thermal stress in the block.