Features:
- Provides 10 analog input channels (configurable for ±10V, 0-20mA, 4-20mA) and 2 analog output channels (4-20mA) for diverse turbine control applications .
- Engineered for fault-tolerant control systems, the board operates in a 2oo3 voting architecture, ensuring high availability and preventing single points of failure in critical processes .
- Rugged design with an operating temperature range of -40°C to +85°C, certified to CE, UL, and Hazardous Location (Class I, Div 2) standards for global deployment in extreme conditions .
The IS200TBAIH1CCC provides a flexible analog interface for Mark VI turbine control systems. With 10 analog input channels, engineers can configure each channel independently for high-level voltage (e.g., ±10V DC) or current loops (0-20 mA or 4-20 mA), making it compatible with common industrial sensors. Additionally, the board features 2 analog output channels designed for standard 4-20 mA control signals to drive actuators.
A standout feature of the IS200TBAIH1CCC is its integration into Triple Modular Redundant (TMR) systems, where it often works with three processors. In this architecture, the board supports the 2oo3 (two-out-of-three) voting logic. This means if one processing path fails or produces an erroneous value, the other two will overrule it, allowing the turbine to continue operating safely without a trip. This fault-tolerant design is essential for preventing costly unplanned shutdowns in power generation.
Built for the extreme conditions of a turbine deck, the IS200TBAIH1CCC is rated for a wide operating temperature range of -40°C to +85°C, allowing it to withstand freezing startups or high radiant heat from the turbine casing . It carries critical safety certifications, including CE for European compliance and UL for North American standards, confirming its reliability for permanent installation.
The IS200TBAIH1CCC GE Industrial Automation Module may still be available for purchase and support from Apter Power beyond
End-Of-Life (EOL) by the manufacturer (OEM).
GE IS200TBAIH1CCC Industrial Automation Module Manuals,
Datasheets, Drivers, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
GE IS200TBAIH1CCC Industrial Automation Module Specs
General
- Manufacturer GE
- Model IS200TBAIH1CCC
- Condition New Original ready stock
- Product Family
IS200TBCIH2BBC,IS200BICLH1AED,IS200TBACIH1B
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
- Gas Turbine Control: Installed in heavy-duty gas turbines (e.g., GE Frame 6B, 7F, and 9F series) to monitor critical variables like fuel gas pressure, fuel oil flow, and compressor discharge pressure (Pcd).
- Steam Turbine Control: Used to log main steam pressure, condenser vacuum levels, extraction pressures, and electro-hydraulic control (EHC) valve position feedbacks.
- Multi-Wire Sensor Ingestion: Equipped with two heavy-duty terminal blocks offering 48 barrier screw terminals.
- EMI/RFI Mitigation: Turbine halls generate massive high-frequency electromagnetic interference from nearby generators and exciters. The TBAI features board-level surge suppression diodes, high-frequency bypass capacitors, and metal oxide varistors (MOVs). These absorb voltage transients and prevent field noise from bleeding into the core VME control backplane.
- One-to-Three Hardware Branching: The defining capability of the TBAI board is its layout of three vertically stacked DC-37 pin high-density cable connectors (labeled JR1, JS1, JT1).
- In a TMR configuration, a single field transmitter is wired into a single terminal block on the TBAI. The internal hardware traces split that exact analog signal three ways, streaming it simultaneously through three independent cables to the R, S, and T control cores.
- Chassis Mounting: The IS200TBAIH1CCC mounts directly onto a standard DIN-rail frame inside the cabinet or on a dedicated metal sheet. Ensure the board's structural ground screw is tightly bound to the enclosure's main ground bar (GND) to unlock the full potential of its noise-filtering circuitry.
- Terminals 1 to 48: Utilize shielded twisted-pair (STP) cables for all analog loops. Connect the cable shield wires directly to the TBAI's designated shield terminals. Ensure shields are grounded at the TBAI end only to prevent dangerous ground loops.
- I/O Pack Connectivity: Once field wires are landed, attach the specialized, shielded high-density DC-37 cables to the JR1, JS1, and JT1 plug ports, tightening the retention locking screws on either side of the hoods.