Features:
- Provides eight individually isolated normally open relay contacts.
- Switches supported AC or DC circuits from one VersaMax position.
- Displays every output command with a dedicated point LED.
General Electric IC200MDL930 provides eight individually isolated Form A contacts, so each channel can use its own field reference instead of a shared common. A contact remains normally open until the host CPU is active and its output bit is set.
External sources power the field loads, allowing the module to switch supported AC and DC circuits from the same VersaMax position. Resistive loads permit up to 2.0 A through 30 VDC or across the specified AC range, while 31 to 125 VDC circuits use a 0.2 A limit.
A dedicated logic-side LED follows each output command, and the OK indicator confirms backplane power. Because the LEDs do not prove that field voltage reaches the load, the external supply and contact wiring should be checked separately.
The General Electric IC200MDL930 VersaMax Relay Output Module may be available with product matching and support from Apter Power.
General Electric IC200MDL930 Isolated Relay Output Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Contact Arrangement
- Contact Form: Eight normally open Form A outputs are provided.
- Circuit Separation: Every output is isolated from the other seven channels.
- Closing Logic: A relay closes when the CPU is active and its output bit is one.
- Field Energy: External supplies provide all load power.
Supported Load Classes
- AC Window: Resistive contacts switch 5 to 265 VAC at up to 2.0 A.
- Low DC Range: Resistive circuits from 5 to 30 VDC allow up to 2.0 A.
- High DC Range: The resistive limit from 31 to 125 VDC is 0.2 A.
- Minimum Current: Each operating load should draw at least 10 mA.
- Contact Drop: Closed-contact voltage drop is 0.3 V maximum.
Relay Operation
- Operate Time: Both ON and OFF response are 10 ms maximum.
- Inductive Duty: The specified switching frequency is 20 cycles per minute for inductive loads.
- Arc Control: Coils and other inductive devices need external suppression.
- Protection Scope: Branch fuses and snubbers are not built into the module.
Module Power and Status
- Backplane Source: VersaMax backplane power operates the module.
- Variable Drain: Five-volt current rises as additional relays energize.
- Point Feedback: Green logic-side LEDs report each channel command.
- Module Health: The OK LED confirms the presence of backplane power.
- Isolation Test: Point-to-point isolation is rated 250 VAC continuously and 1500 VAC for one minute.