Horner HE800DIQ716 is a mixed SmartStack DC I/O module that reads sixteen 12/24 VDC signals and drives twelve positive-logic loads.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for HE800DIQ716
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for HE800DIQ716

  • Manufacturer:
    HORNER
  • Part Number:
    HE800DIQ716
  • Product Family:
    HORNER
  • Product Type:
    16-Input 12-Output Mixed DC I/O Module
  • Stock:
    1
  • Digital Inputs:
    16
  • Input Range:
    12–24 VDC
  • DC Outputs:
    12
  • Output Range:
    10–28 VDC
  • Load per Channel:
    0.5 A max.
  • Weight:
    256 g
  • Weight:
    0.564 lbs (0.256 kg)
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Sourcing Drive Output Protection Load Power Channel Derating

Features:

  • Reads sixteen bidirectional 12/24 VDC input channels.
  • Drives twelve positive-logic DC loads.
  • Protects sourcing outputs against short circuits.
Horner HE800DIQ716 is the metal SmartStack version of the DIQ716 mixed-DC-I/O design; HE-DIQ716 identifies the plastic-case form.

The solid-state output bank makes this configuration suitable for fast DC actuators that do not require dry relay contacts.

Match the field-supply range, current derating, input commons and safe stop-state behavior to the installed control scheme.

The Horner HE800DIQ716 Mixed DC I/O Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Horner HE800DIQ716 16-Input 12-Output Mixed DC I/O Module Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

HE800DIQ716 Positive-Logic Output Operation

  • Output Mode: Twelve channels source current to positive-logic loads.
  • Operating Range: Field output power is 10–28 VDC.
  • Channel Current: Maximum load is 0.5 A per output.
  • Pull-Down: Each output includes a 10 kΩ pull-down path.

HE800DIQ716 Electronic Output Safeguards

  • Short Circuit: The sourcing channels include short-circuit protection.
  • Peak Voltage: Output voltage must not exceed 28 VDC.
  • Transient Device: The output circuit uses 33 VDC, 600 W transorbs.
  • Recovery Check: Field wiring and load faults should be cleared before reuse.

HE800DIQ716 Field Supply and Load Limits

  • Power Feeds: V1, V2 and V3 supply the three four-output sections.
  • Shared Return: The twelve outputs use one common connection.
  • Inrush Rating: Maximum module inrush is specified at 650 mA.
  • No Minimum Load: The output specification lists no minimum load.

HE800DIQ716 Current Capacity by Temperature

  • Temperature Span: Operation is specified from 0°C to 60°C.
  • Current Curve: Permissible channel loading decreases according to the derating chart.
  • Switching Speed: Both output transitions are 1 ms.
  • Ambient Moisture: Relative humidity is 5–95% non-condensing.
Description
Horner HE800DIQ716 combines sixteen bidirectional 12/24 VDC inputs with twelve current-sourcing DC outputs. Unlike relay-based mixed I/O, its solid-state output section provides 1 ms switching and positive-logic load control across a 10–28 VDC operating range.

The input channels of Horner HE800DIQ716 are arranged in three isolated common groups, while the output field supply is connected through three load-power terminals sharing one output common. Each output can deliver up to 0.5 A and includes short-circuit protection; total usable load must still follow the temperature derating limits.

Cscape can monitor the module’s I/O and define what each output does when the controller enters idle or stop. Horner HE800DIQ716 defaults to outputs OFF, making careful review essential before selecting ON or hold-last-state behavior for any connected actuator.
Alternative Names
HE800-DIQ716 HE 800 DIQ 716 HE800 DIQ716 HEDIQ716 HE-DIQ716 Horner HE800DIQ716 SmartStack DIQ716 HE800DIQ716 DC I/O
Technical notes
Horner HE800DIQ716 pairs sixteen bidirectional inputs with twelve 10–28 VDC sourcing outputs. Each output is rated 0.5 A maximum and includes short-circuit protection.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why will a Horner HE800DIQ716 output not energize even though its logic state is ON?
Horner HE800DIQ716 needs 10–28 VDC field power at the corresponding load-power terminal; verify V1, V2 or V3 and the shared output common.
Can Horner HE800DIQ716 drive a 0.5 A DC load on every channel at once?
Horner HE800DIQ716 rates each sourcing output to 0.5 A maximum, but simultaneous loading must also satisfy the module’s temperature derating chart.
What happens when Horner HE800DIQ716 detects an output short circuit?
Horner HE800DIQ716 includes short-circuit protection on its current-sourcing outputs; correct the field fault and confirm the channel and supply before returning the load to service.
Can Horner HE800DIQ716 inputs use opposite field polarities?
Horner HE800DIQ716 has bidirectional inputs supporting positive- or negative-logic wiring, with each isolated common group connected consistently for its field devices.
Why can controller scan time matter even though Horner HE800DIQ716 switches in 1 ms?
Horner HE800DIQ716 specifies 1 ms input and output transitions, but observed machine response also includes the PLC scan and application-logic execution time.
How can Horner HE800DIQ716 preserve an actuator state during a controller stop?
Horner HE800DIQ716 can set individual outputs to ON, OFF or hold last state in Module Setup, although OFF is the default and safety implications must be reviewed.