Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail info@apterpower.com

RH916JT

/ 4.9
1001 reviews | Need a Specific Revision?
Foxboro RH916JT is a DIN-rail compression termination assembly for FBM211 channels using customer-supplied external DC loop power.
In Stock
Ships by Saturday, October 17
Fast Shipping Available
Get a quick price for RH916JT
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for RH916JT

  • Manufacturer:
    Invensys
  • Part Number:
    RH916JT
  • Product Family:
    Foxboro
  • Product Type:
    FBM211 Externally Powered Compression Termination Assembly
  • Stock:
    1
  • Terminal style:
    DIN-rail compression terminals
  • Loop-power method:
    Customer-supplied external DC loop power
  • Compatible module:
    FBM211
  • Required termination cable:
    Type 4, ordered separately
  • Operating temperature:
    -20 to 70°C
  • Dimensions:
    12.7 × 8.0 × 12.5 cm
  • Height above DIN rail:
    7.2 cm
  • Cable connector:
    37-pin male D-subminiature
  • Terminal blocks:
    Inputs - 2 tiers, 16 positions
  • Accepted solid/stranded wire:
    0.2 to 4 mm² / 0.2 to 2.5 mm²; 24 to 12 AWG
  • Accepted stranded wire with ferrules:
    0.2 to 2.5 mm², with or without plastic collar
  • Weight:
    0.272 kg
  • Tariff Code:
    8536909000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals External Power Field Terminals Troubleshooting Application
  • Terminates sixteen FBM211 field circuits
  • Uses customer-supplied external DC loop power
  • Requires the separately ordered Type 4 termination cable

Foxboro RH916JT provides the field-terminal interface between an FBM211 input module and sixteen transmitter or supervised-contact circuits.

RH916JT provides passive compression terminals for FBM211 loops powered from a separately engineered field supply.

The assembly is passive field-wiring hardware; signal conversion and channel configuration remain in the FBM211, while the Type 4 termination cable is ordered and verified separately.

Availability, condition, price, and shipping time for RH916JT are confirmed during quotation.

Foxboro RH916JT Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Identify the customer loop supply and distribution path
  • Verify voltage, polarity, fusing and grounding under load
  • Keep the external supply separate from FBM auxiliary power
  • Preserve compression-terminal channel numbering
  • Record shared returns and shield bonding before removal
  • Match conductor preparation and cabinet clearances
  • Measure field supply at the TA rather than at the source only
  • Inspect the Type 4 connector when a whole group is affected
  • Compare known loop current with the FBM engineering value
  • Externally powered 4–20 mA transmitter termination
  • Customer-supplied DC loop distribution for FBM211
  • Supervised contact circuits with independent field power
Description
Foxboro RH916JT provides the field-terminal interface between an FBM211 input module and sixteen transmitter or supervised-contact circuits.

RH916JT provides passive compression terminals for FBM211 loops powered from a separately engineered field supply.

The assembly is passive field-wiring hardware; signal conversion and channel configuration remain in the FBM211, while the Type 4 termination cable is ordered and verified separately.
Alternative Names
RH916JT RH 916 JT FBM211 RH916JT Foxboro RH916JT Invensys RH916JT Invensys Foxboro RH916JT FBM211 P0916JT
Technical notes
RH916JT is a termination assembly, not an FBM211 electronic module. Its dimensions and approximately 0.272 kg net weight must not be copied to the FBM211 module record.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
When is Foxboro RH916JT preferable to RH916BT?
Use RH916JT when the installed FBM211 loops are powered from a verified customer field supply rather than from the FBM auxiliary +24 VDC source.
Does Foxboro RH916JT regulate or protect the external loop supply?
Do not treat it as a power conditioner. The external supply, distribution, fusing, grounding and intrinsic-safety design remain part of the field circuit.
What must match before Foxboro RH916JT replaces another compression TA?
Match the exact TA code, Type 4 cable, channel terminal map, loop-power method, conductor size and DIN-rail space.
Why can all loops on Foxboro RH916JT read low after replacement?
Check the external supply under load, shared return and polarity, Type 4 cable seating, group references and whether the TA was confused with an auxiliary-powered version.
Can Foxboro RH916JT be used for intrinsically safe loops by itself?
No. Any barrier, isolator, grounding and hazardous-area approval must be provided by the approved loop design; the TA alone does not create intrinsic safety.
What should be recorded before disconnecting Foxboro RH916JT?
Record external supply and return points, every terminal, shield bonding, cable code, conductor identification and the live current of critical loops.
How should Foxboro RH916JT be commissioned?
Confirm external supply polarity and voltage, inject known signals into both channel groups, verify scaling and open-loop diagnostics, and inspect terminal security after loading.