Features:
- Triple Modular Redundant (TMR) architecture with 32 digital input points grouped into four isolated banks of eight.
- Low voltage switching threshold operating at 20 to 42.5 VDC, featuring <12 VDC Off-to-On and >4 VDC On-to-Off levels.
- Automated internal self-test routine for continuous detection of stuck-On field input and circuit failures.
The Schneider Triconex 3505E is available as a brand-new or fully tested surplus 24 VDC Low Threshold TMR Digital Input Module, supplied in original or protective ESD packaging ready for critical safety system installation.
Designed for high-integrity Safety Instrumented Systems (SIS), this module conditions incoming discrete signals across three triplicated processing paths to deliver fault-tolerant logic voting for emergency shutdown (ESD) and process safety applications.
When integrating into a Tricon chassis, ensure proper backplane slot keying alignment, connect exclusively to approved external termination panels (ETP) via system cables, and configure the software I/O definitions prior to online module insertion.
The Schneider Triconex 3505E TMR DI Module availability and lead times are subject to stock verification by the manufacturer (OEM) or authorized vendor.
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Emergency Shutdown Systems (ESD) requiring low-threshold discrete field switch monitoring.
- Burner Management Systems (BMS) for critical valve position and flame switch signal verification.
- Fire and Gas (F&G) detection networks utilizing 24 VDC discrete field transmitters.
- Delivers high-speed response with input delays under 8 ms for Off-to-On transitions and under 15 ms for On-to-Off transitions.
- Operates with low field power dissipation of 0.5 watts per active point, reaching a maximum of 1.5 watts at 42.5 VDC.
- Requires low turn-on current between 3 mA and 5 mA, making it ideal for low-power discrete field contacts.
- Features front-panel PASS, FAULT, and ACTIVE status indicators for fast visual health checking.
- Includes 32 individual point status LEDs providing direct real-time visual monitoring of field channel states.
- Scans field inputs independently via microprocessor channels and transmits voted logic data to Main Processors.
- Certified for operation in process control environments with an ambient operating temperature rating up to 140°F (60°C).
- Features optional conformal coating (model suffix C) to protect internal circuit assemblies against corrosive atmospheric environments.
- Select conformally coated hardware configurations are certified for use in harsh marine operational environments.