Features:
- Controls sixteen isolated 115 VAC field points without a shared output common.
- Handles a twelve-amp surge for one AC cycle while maintaining a two-amp maximum continuous rating per point.
- Offers 1,500 VDC point isolation in 3601E and 2,500 VDC point isolation in 3601T.
The current ordering configuration covers 3601E and 3601T, the 115 VAC variants in the Tricon sixteen-point TMR digital-output range.
These modules source current to independently wired AC loads and use voltage feedback to reveal a switch, field-power, load, or fuse condition that conflicts with the controller command.
Before installation, identify the required isolation version, verify the 80-155 VAC operating range, and match every output conductor to the specified external termination panel and cable.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Triconex 3601E/3601T:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Switches 115 VAC solenoids, relays and shutdown devices from voted Tricon logic.
- Provides high-integrity discrete actuation for burner management, emergency shutdown and machine-protection sequences.
- Supports planned online maintenance where a correctly configured hot-spare position and ETP are available.
- The non-commoned architecture keeps individual AC field circuits separated through the approved termination arrangement.
- Point isolation is rated at 1,500 VDC for 3601E and 2,500 VDC for the 3601T configuration.
- Field design must account for the specified chassis and load leakage when connecting sensitive coils or monitoring devices.
- The 3601T variant is identified among the Tricon equipment qualified for nuclear 1E applications under the documented program.
- Standard equipment specifications continue to apply where a nuclear-qualified model is selected for the approved installation.
- Qualification does not make E and T suffixes interchangeable; the exact module, termination hardware and project documentation must agree.
- Each output uses a 3 A fast-acting fuse located on the selected field termination panel.
- Because the module sources current but does not create load power, the AC field source must be wired to every output point.
- The E and T variants must be paired with the approved cable and termination-panel option for their commoning and isolation requirements.