Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power supports Siemens 6MF1013-0CF51-0AA0 documentation, configuration matching, and quotations.

6MF1013-0CF51-0AA0

/ 4.9
1001 reviews | Need a Specific Revision?
Siemens 6MF1013-0CF51-0AA0 is a SICAM AK 3 SM-2551 serial interface processor that adds two isolated serial channels to CP-2016 or CP-2019 carrier modules.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for 6MF1013-0CF51-0AA0
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 6MF1013-0CF51-0AA0

  • Manufacturer:
    Siemens
  • Part Number:
    6MF1013-0CF51-0AA0
  • Product Family:
    Siemens SICAM A8000 Serie
  • Product Type:
    SICAM AK-3 SM-2551 Serial Interface Processor 2 SI
  • Stock:
    1
  • Serial Interfaces:
    2
  • Carrier Modules:
    CP-2016 and CP-2019
  • Interface Connectors:
    X2 and X3
  • Signal Processing:
    Byte-asynchronous or byte-isochronous pulse code modulation
  • Parallel Operation:
    Up to 2 interfaces
  • Outgoing Interface Signals:
    Tristate technology
  • Incoming Interface Circuits:
    Always active
  • Galvanic Isolation:
    From logic circuits and between the two interfaces
  • V.28 Line Length at 50 bit/s:
    Up to 25 m
  • V.28 Line Length at 115200 bit/s:
    Up to 5 m
  • Operating Voltage:
    4.75–5.25 V DC
  • Current Consumption:
    300 mA typical; 540 mA maximum at 5 V
  • Gate Circuit Voltage:
    4.7–5.6 V DC instead of DSR
  • Gate Output Current:
    150 mA maximum at U > 4.75 V
  • Gate Output Protection:
    Not short-circuit-proof and not overload-proof
  • Weight:
    0.441 lbs (0.2 kg)
  • Estimated shipping dimensions:
    22.73 × 6.35 cm
  • Tariff Code:
    85176200
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Interface Paths Parallel Signalling Isolation & Gate Power Carrier Integration

Features:

  • Siemens 6MF1013-0CF51-0AA0 is the SM-2551 two-interface serial processor identified by item code BC2-551.
  • The module uses X2 and X3 on a CP-2016 or CP-2019 carrier for its two serial communication paths.
  • Both interfaces are galvanically separated from the logic circuits and from each other.
The carrier position places 6MF1013-0CF51-0AA0 between the supplementary system-element bus and the external serial connection. Operating power enters from the carrier rather than a separate terminal.

Each path on 6MF1013-0CF51-0AA0 can handle byte-asynchronous or byte-isochronous pulse-code operation. The supported interface characteristics are selected with the relevant protocol configuration.

When parallel wiring is used, 6MF1013-0CF51-0AA0 places outgoing signals in tristate operation while keeping incoming circuits active. The V.28 cable limit then changes with the selected bit rate.

The Siemens 6MF1013-0CF51-0AA0 SICAM AK 3 SM-2551 Serial Interface Processor may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6MF1013-0CF51-0AA0 SICAM AK 3 SM-2551 Serial Interface Processor Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Two Serial Channels on the Carrier

  • Channel count: 6MF1013-0CF51-0AA0 provides two independent serial communication circuits.
  • Connector X2: The first serial path reaches the external connection through X2 on the carrier module.
  • Connector X3: The second serial path uses X3, keeping the two communication paths separately identifiable.
  • Protocol setting: Electrical characteristics and signal assignments follow the selected protocol mode rather than a single fixed pin function.

Signal Behaviour in a Shared Connection

  • Parallel limit: Up to two interfaces can be connected in parallel for the supported operating mode.
  • Outgoing path: Transmitted interface signals use tristate technology so their driven state can be controlled.
  • Incoming path: Receive circuits remain active while the outgoing side changes state.
  • Mode selection: Byte-asynchronous and byte-isochronous pulse-code modes are selected through the applicable protocol configuration.

Separated Signal and Auxiliary Paths

  • Logic separation: Serial signals are galvanically isolated from the module logic circuits.
  • Channel separation: The two interface circuits are also galvanically isolated from each other.
  • Gate voltage: A carrier-supplied 4.7–5.6 V DC gate voltage can be selected instead of the DSR signal.
  • Protection limit: The gate-voltage output is neither short-circuit-proof nor overload-proof, so the connected load must remain within its stated limit.

How the SM-2551 Fits the Basic Element

  • Supported carriers: The SM-2551 is installed on CP-2016 or CP-2019 basic system elements.
  • Power source: The carrier supplies 4.75–5.25 V DC to 6MF1013-0CF51-0AA0.
  • Current budget: Carrier planning must allow 300 mA typical and 540 mA maximum at 5 V.
  • Cable-rate relation: V.28 permits up to 25 m at 50 bit/s but only up to 5 m at 115200 bit/s.
Description
The Siemens 6MF1013-0CF51-0AA0 is the SM-2551 serial interface processor in the SICAM AK 3 system. It handles two serial communication paths between the carrier logic and connected field-side communication equipment.

Installed on a CP-2016 or CP-2019 carrier, 6MF1013-0CF51-0AA0 uses connectors X2 and X3 for its two serial paths. The carrier supplies the operating voltage, so the serial module does not use a separate field-power input.

During parallel operation, up to two interfaces can share the connection arrangement of 6MF1013-0CF51-0AA0. Outgoing signals use tristate technology while the incoming interface circuits remain active, and the two interfaces are galvanically isolated from the logic circuits and from each other.

For the V.28 path, 6MF1013-0CF51-0AA0 allows up to 25 m at 50 bit/s and up to 5 m at 115200 bit/s. The permitted cable distance therefore depends on the selected transmission rate rather than on the connector alone.
Alternative Names
6MF10130CF510AA0 6MF1013 0CF51 0AA0 6MF 1013-0CF51-0AA0 Siemens 6MF1013-0CF51-0AA0 SM-2551 6MF1013-0CF51-0AA0 BC2-551 6MF1013-0CF51-0AA0 6MF1013 0CF51-0AA0 6MF1013-0CF5I-0AA0
Technical notes
On Siemens 6MF1013-0CF51-0AA0, X2 and X3 carry the two serial paths, while the carrier module supplies operating power and isolated gate voltage.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why must the carrier type be checked before installing Siemens 6MF1013-0CF51-0AA0?
Siemens 6MF1013-0CF51-0AA0 is an installable serial interface module for CP-2016 and CP-2019 carriers; another carrier must not be assumed from the connector shape.
Which connectors carry the two channels of Siemens 6MF1013-0CF51-0AA0?
The two serial paths of Siemens 6MF1013-0CF51-0AA0 use X2 and X3 on the supported carrier, so both connector assignments must be checked during replacement.
How does transmission rate affect a V.28 cable run on Siemens 6MF1013-0CF51-0AA0?
Siemens 6MF1013-0CF51-0AA0 permits up to 25 m at 50 bit/s but only up to 5 m at 115200 bit/s, so the rate must be selected before cable length is accepted.
What changes when two interfaces are wired in parallel on Siemens 6MF1013-0CF51-0AA0?
With Siemens 6MF1013-0CF51-0AA0, outgoing interface signals use tristate technology while incoming circuits remain active, and no more than two interfaces may be paralleled.
Can the gate-voltage output of Siemens 6MF1013-0CF51-0AA0 tolerate a short circuit?
No. The gate-voltage output on Siemens 6MF1013-0CF51-0AA0 is not short-circuit-proof or overload-proof and must remain within its 150 mA limit.
Where does Siemens 6MF1013-0CF51-0AA0 obtain its operating power?
Siemens 6MF1013-0CF51-0AA0 receives 4.75–5.25 V DC from the carrier module, so no separate field-power input should be assigned to the serial board.