Features:
- A selector separates the 120 V and 230 V class input windows.
- The isolated 24 V output is adjustable and follows a U-I overload characteristic.
- Two identical supplies may be paralleled within the documented current limits.
Siemens 6EP1334-1LB00 routes single-phase power through L1, N and PE before producing the isolated DC control supply.
Rated current remains 10 A through +45 °C and changes to 7 A at the +60 °C operating boundary.
The paired output screws simplify conductor landing but do not divide the secondary into independently regulated channels.
The Siemens 6EP1334-1LB00 SITOP PSU100L 24 V DC 10 A Stabilized Power Supply may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6EP1334-1LB00 SITOP PSU100L 24 V 10 A Supply Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Selector and Input Wiring
- Source terminals: Single-phase supply enters through L1 and N, with PE connected to the protective conductor.
- Lower window: The 120 V class setting covers 93 to 132 V AC.
- Upper window: The 230 V class setting covers 187 to 264 V AC.
- Feeder protection: The documented line feeder uses a characteristic-C miniature circuit breaker rated from 10 A.
Current Rating Across Temperature
- Rated region: The full 10 A output is available from 0 through +45 °C.
- Warm boundary: At +60 °C the permitted output current is 7 A.
- Cooling path: Natural convection carries heat away from the rail-mounted housing.
- Conductor sizing: Output cables must be selected for the maximum rms current used in the installation.
Overload and Short-Circuit Response
- Voltage regulation: The selected DC voltage is maintained until the load reaches the U-I boundary.
- U-I response: Beyond the boundary, output voltage and current follow the documented U-I curve.
- Short circuit: The output remains protected with a typical continuous short-circuit current of 12.6 A.
- Voltage ceiling: Secondary overvoltage protection keeps the output below 33 V.
Shared-Bus Conditions
- Maximum quantity: Power expansion permits no more than two matching supplies.
- Common voltage: Both potentiometers must be aligned before the outputs are joined.
- Terminal use: The duplicated positive and negative screws give each conductor a landing point on the common bus.
- Load check: The combined arrangement still follows the specified thermal current limits for each supply.