IC200UDR440

/ 4.9
1001 reviews | Need a Specific Revision?
The General Electric IC200UDR440 is a 40-point VersaMax Micro PLC used to monitor twenty-four DC input signals and switch sixteen externally powered relay loads from a 12/24 VDC control supply.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for IC200UDR440
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for IC200UDR440

  • Manufacturer:
    General Electric
  • Part Number:
    IC200UDR440
  • Product Family:
    GE VersaMax
  • Product Type:
    VersaMax Micro 40-Point Relay PLC
  • Stock:
    1
  • Input Points:
    24
  • Input Logic:
    24 VDC positive/negative
  • Output Points:
    16
  • Output Type:
    Normally open Form A relay, 2 A per circuit
  • Controller Supply:
    12/24 VDC nominal; 19.2 to 30 VDC range
  • Auxiliary 24 VDC:
    435 mA maximum
  • High-Speed Counters:
    Up to four; 100 kHz maximum
  • Input Response:
    1 to 20 ms configurable; 100 us HSC
  • Isolation:
    1500 V RMS field-to-logic; 500 V RMS between groups
  • Serial Interface:
    RS-232 with SNP/SNPX, Modbus RTU and Serial I/O
  • Estimated shipping dimensions:
    15 x 9 x 7.6 cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Connectivity Memory Backup Installation Applications

Features:

  • Integrates twenty-four configurable DC inputs with sixteen Form A relay outputs.
  • Processes designated high-speed input signals at rates up to 100 kHz.
  • Uses removable field terminals and supports four expansion units.
The 12/24 VDC-powered base unit suits control panels that need a larger relay-output count without moving to a separate rack.

A 435 mA auxiliary 24 VDC source is available for compatible field devices, while each I/O point has a local state indicator for commissioning checks.

Program storage, register capacity and optional communication modules let the controller handle standalone logic as well as linked machine-control duties.

The General Electric IC200UDR440 VersaMax Micro 40-Point PLC may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IC200UDR440 VersaMax Micro PLC Manuals, Datasheets, LinksImportant Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Available Communication Paths

  • Primary Port: The controller includes a built-in RS-232 interface.
  • GE Protocols: SNP and SNPX master or slave roles are supported.
  • Open Protocol: Modbus RTU communication can operate as master or slave.
  • Port Expansion: Optional boards can add a second serial, USB or Ethernet-related path.

Application Storage Strategy

  • Logic Capacity: Up to 24K words are available for the control program.
  • Data Capacity: The register area provides 32K words for application values.
  • Power-Up Choice: Startup can use RAM or a stored flash configuration.
  • Retention: Capacitor backup covers about thirty minutes and an optional lithium battery extends support.

Wiring and Expansion Practices

  • Controller Feed: Supply the base from the documented 19.2–30 VDC operating range.
  • Load Circuits: Relay devices need external field power and suitable suppression.
  • Terminal Access: Four removable strips divide the field wiring into serviceable sections.
  • Chain Limit: Up to four expansion units may share the permitted two-meter connection span.

High-Speed Counting Roles

  • Flow Measurement: Turbine-meter pulses can be accumulated at high speed.
  • Position Tracking: Encoder counts can represent travel or material position.
  • Speed Monitoring: Pulse frequency can support velocity calculations and control.
  • Process Sequencing: Fast input events can trigger time-critical machine steps.
Description
General Electric IC200UDR440 is a 40-point VersaMax Micro controller that receives twenty-four 24 VDC input signals and controls sixteen relay-output circuits. The controller itself uses a 12/24 VDC supply, while field loads obtain power through the relay commons from their own external source.

Its inputs can follow either positive- or negative-logic wiring, which makes the base unit adaptable to different sensor conventions. The first eight inputs can participate in high-speed counter arrangements up to 100 kHz for tasks such as turbine flow measurement, velocity monitoring and material-handling position detection.

The sixteen normally open Form A contacts can switch AC or DC devices and may be assigned to high-speed counter output functions. They do not generate pulse-train or PWM signals, so motion commands that require those waveforms need a different output arrangement.

Communication is built around an RS-232 port that supports SNP/SNPX, Modbus RTU and Serial I/O roles, with an optional second-port module available for broader connectivity. Removable terminal assemblies and support for four expansion units simplify service and later I/O growth without replacing the controller.
Alternative Names
GE IC200UDR440 IC200 UDR440 VersaMax Micro IC200UDR440 IC200-UDR440 IC200UDR440 GE Fanuc IC200UDR440 IC200 UDR 440 IC200UDR44O
Technical notes
General Electric IC200UDR440 provides 24 configurable inputs and 16 Form A relay outputs in a 12/24 VDC VersaMax Micro PLC. Verify input logic, relay grouping and external load power.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How can field wiring be serviced without removing every conductor from General Electric IC200UDR440?
Removable terminal assemblies on General Electric IC200UDR440 allow conductors to stay landed while the controller is replaced. Label each strip and isolate field power before disconnecting it from the base unit.
Why cannot General Electric IC200UDR440 generate a PWM command from its relay bank?
The outputs on General Electric IC200UDR440 are mechanical Form A contacts intended for switched AC or DC loads. They can support assigned counter-output functions, but they do not provide PTO or PWM waveforms.
What communication path is available when General Electric IC200UDR440 needs a supervisory link?
General Electric IC200UDR440 includes a built-in RS-232 interface for SNP/SNPX, Modbus RTU and Serial I/O roles. An optional second-port module can be selected when the installation needs another supported connection.
How should relay commons be arranged when General Electric IC200UDR440 controls mixed voltages?
Separate the relay groups of General Electric IC200UDR440 according to field voltage and source. Never combine incompatible AC and DC circuits on one common, and provide suitable branch protection and suppression for each load group.
What helps General Electric IC200UDR440 match an existing PNP or NPN sensor scheme?
Input groups on General Electric IC200UDR440 accept either positive- or negative-logic wiring. Choose the convention that matches the installed sensors, then apply it consistently across every point sharing that common.
Can General Electric IC200UDR440 count pulses from a turbine flowmeter?
Yes. Designated inputs on General Electric IC200UDR440 support high-speed counting up to 100 kHz for compatible pulse sources. Confirm signal level, shielding, counter mode and scaling before using the count as a flow value.