Technical specifications for FBM245

  • Manufacturer:
    Invensys
  • Part Number:
    FBM245
  • Product Family:
    Foxboro
  • Product Type:
    Redundant 0-20 mA I/O Module with HART Support
  • Stock:
    1
  • Analog inputs:
    4 isolated redundant channels, 0 to 20.4 mA DC
  • Input accuracy:
    ±0.075% of span
  • Analog outputs:
    4 isolated redundant channels, 0 to 20.4 mA DC
  • Output accuracy:
    ±0.05% of span at 25°C from 4 to 20 mA
  • Output load:
    735 Ω maximum
  • Output compliance:
    18.0 V nominal at 20 mA at field terminals
  • Output resolution:
    12 bits
  • Output settling time:
    100 ms to 1% band for a 10-90% step
  • Isolation test:
    600 VAC for one minute
  • Power consumption:
    7 W maximum
  • Heat dissipation:
    3 W maximum
  • Module Fieldbus:
    Redundant 2 Mbps
  • Input power:
    24 VDC +5%, -10%
  • Operating temperature:
    -20 to +70°C
  • Storage temperature:
    -40 to +70°C
  • Relative humidity:
    5 to 95%, noncondensing
  • Contamination class:
    ISA-S71.04 Class G3
  • Dimensions:
    10.2 × 4.5 × 10.4 cm
  • Weight:
    0.284 kg
  • Tariff Code:
    8538900000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Analog Inputs Analog Outputs Redundancy Application
  • Use FBM245 only for the documented FBM245 channel function
  • Confirm the electronic-module order number, termination hardware and cable before replacement
  • Preserve field wiring, channel configuration, diagnostics and redundancy state before removal

FBM245 is a Foxboro redundant 0-20 ma i/o module with hart support designed for Foxboro DCS 200 Series field I/O.

Foxboro FBM245 is a redundant mixed analog I/O module with four isolated inputs, four isolated outputs and HART 5/6/7 support. FBM245 is the official functional model and RH927AL is its current exact module part number; RH924DU is the separate redundant adapter.

Before installation or replacement, verify the complete nameplate, companion hardware, termination assembly, cable, signal limits, field wiring, saved configuration and supported system environment.

Availability, condition, price, and shipping time for FBM245 are confirmed during quotation.

Foxboro FBM245 Redundant 0-20 mA I/O Module with HART Support Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Use four isolated 0-20.4 mA redundant input channels
  • Apply the documented ±0.075% span accuracy boundary
  • Confirm field-device power, polarity and HART compatibility for every loop
  • Use four isolated 0-20.4 mA redundant output channels
  • Keep total output burden at or below 735 Ω
  • Verify 18.0 V nominal compliance at 20 mA at the field terminals
  • Install the pair with the documented RH924DU redundant adapter
  • Preserve input/output scaling and HART device records
  • Prove signal continuity and diagnostics during approved transfer testing
  • Redundant 4-20 mA transmitter input acquisition
  • Redundant 4-20 mA valve and actuator output control
  • Mixed HART measurement and control loops using one redundant I/O module pair
Description
FBM245 is a Foxboro redundant 0-20 ma i/o module with hart support for the Foxboro DCS 200 Series I/O platform.

Foxboro FBM245 is a redundant mixed analog I/O module with four isolated inputs, four isolated outputs and HART 5/6/7 support. Its documented channel architecture and electrical limits define the supported field interface.

Before installation or replacement, confirm the complete FBM245 identity, module part number, compatible termination hardware, cable, field power, wiring, saved configuration and control-system requirements.
Alternative Names
FBM245 FBM 245 Foxboro FBM245 Foxboro Evo FBM245 Invensys Foxboro FBM245 I/A Series FBM245 RH927AL FBM245 RH927AL
Technical notes
FBM245/RH927AL combines four redundant analog inputs and four redundant analog outputs with HART support. Use RH924DU only as the separate adapter.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can FBM245 replace another mixed analog or HART module without engineering changes?
No. Confirm the RH927AL identity, redundant partner, RH924DU adapter, termination assembly, cable, input and output mapping, scaling, HART device records and downloaded configuration.
What hardware and project details should be checked before ordering FBM245?
Verify both module labels, partner compatibility, RH924DU adapter, termination assembly, cable, adjacent baseplate positions, field wiring, system release and approved project documentation.
Why can a loop carry analog current while HART communication fails on FBM245?
Check the device mode and identity, loop resistance, cable route, barriers, polarity, grounding, noise, adapter and termination path, and the restored HART configuration.
Why might an FBM245 input remain BAD or an output fail to reach the commanded value?
Check field power, loop continuity, polarity, total burden, input and output scaling, channel assignment, field-device condition, adapter connections, alarms and active diagnostics.
What should be recorded before replacing FBM245?
Record both module labels, active and tracker state, adapter, termination assembly, cable, input and output mapping, scaling, HART device identities, alarms and diagnostics.
How should FBM245 analog loops be validated after installation or replacement?
Inject traceable currents on every used input, command controlled output points, independently measure each loop, and verify scaling, polarity, HART communication, alarms and diagnostics.
How should FBM245 redundant transfer be accepted?
Under an approved procedure, confirm partner health and synchronization, continuous input quality and output current, HART communication, expected alarms and diagnostic recovery.