Features:
- Reads sixteen differential thermocouple points with channel isolation.
- Supports J, K, T and E thermocouple types selected in TriStation 1131.
- Adds a dedicated cold-junction fault indicator to the standard module diagnostics.
This isolated thermocouple module is the sixteen-point option that includes support for type E in addition to J, K and T.
Each TMR input path performs linearization and cold-junction compensation before sending temperature data to the processors.
Successful selection depends on one common sensor type, correct polarity, appropriate burnout direction and a thermally uniform ETP.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Triconex 3708E:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Monitors furnace, reactor and combustion temperatures using supported thermocouple types.
- Provides isolated temperature acquisition for safety trips and permissive logic.
- Detects cold-junction transducer problems through the dedicated front-panel indication.
- Reference-junction compensation is specified for a 0°C to 60°C operating interval.
- J, K, T and E thermocouple types provide the documented sensor choices for measured temperature.
- Usable measurement limits follow the selected thermocouple type and its configured linearization.
- All sixteen channels are configured for one thermocouple type rather than mixed sensor types.
- Burnout direction is selected in TriStation 1131 to match the required failure response.
- Channel assignments and signed temperature scaling must correspond to the connected field sensors.
- A dedicated CJ Fault indication identifies a failed cold-junction transducer.
- Pass, Fault and Active indicators report the operating state of the module and acquisition paths.
- Each input point is protected for continuous exposure up to the documented 110 VAC level.