Features:
- The PROFIBUS-DP interface maps a remote station of up to eight S7-300 modules.
- Separate 128-byte input and output areas carry cyclic station data.
- High Feature functions include time stamping, redundancy, and isochronous operation in supported configurations.
The 24 V input of 6ES7153-2BA00-0XB0 also supports the internal 5 V backplane supply for the installed station modules.
Address and baud-rate settings on 6ES7153-2BA00-0XB0 must agree with the configured DP master and segment.
Time events stored by 6ES7153-2BA00-0XB0 are transferred through finite message buffers rather than an unlimited history.
The Siemens 6ES7153-2BA00-0XB0 ET 200M IM153-2 High Feature Interface Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7153-2BA00-0XB0 ET 200M IM153-2 High Feature Interface Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
PROFIBUS Station Exchange
- Physical layer: The isolated RS485 port connects the station to the PROFIBUS segment.
- Addressing: The configured station address remains between 1 and 125.
- Data rate: The network can operate at supported rates up to 12 Mbit/s.
- DP services: SYNC, FREEZE, and sender functions depend on the master configuration.
Event Capture and Buffering
- Resolution: Supported digital events are recorded with 1 ms resolution.
- Input count: As many as 128 digital input points can participate.
- Buffers: Fifteen buffers hold twenty timestamp messages each.
- Transfer: Recorded events move to the master through the configured DP communication path.
High Feature Operating Modes
- Interface pair: A supported redundant station uses the documented pair arrangement.
- Switchover: Station data follows the active communication path during a master change.
- Isochronous mode: Cycle synchronization requires matching master and station configuration.
- Consistency: Hardware configuration, GSD data, and installed modules must describe the same station.
Backplane and Module Chain
- Module count: The interface manages up to eight installed S7-300 modules.
- Address image: The complete chain remains within 128 input and 128 output bytes.
- Backplane supply: The interface provides up to 1 A at 5 V DC to the station bus.
- Environment: IP20 construction operates from 0 to 60 °C inside the enclosure.