  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power can align the DH-485 link, L1 DC supply and installed application with the requested spare.

2711-B6C3L1

/ 4.9
1001 reviews | Need a Specific Revision?
Allen-Bradley 2711-B6C3L1 is a PanelView Standard 600 color keypad-and-touch terminal with DH-485 controller communication and 24 V DC power.
In Stock
Ships by Saturday, November 14
Fast Shipping Available
Get a quick price for 2711-B6C3L1
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 2711-B6C3L1

  • Manufacturer:
    Allen-Bradley
  • Part Number:
    2711-B6C3L1
  • Product Family:
    PanelView
  • Product Type:
    PanelView Standard 600 Color Keypad and Touch Terminal
  • Stock:
    1
  • Operator Input:
    Dual Input (Keypad and Touchscreen)
  • Memory:
    240 KB
  • Display Type:
    Color Active Matrix TFT
  • Display Size:
    5 in.
  • Communication Port:
    DH-485 Communication Port
  • Input Power:
    18-32 VDC
  • Input Voltage:
    24V DC
  • Configuration Software:
    PanelBuilder32
  • Weight:
    2.3 kg
  • Estimated shipping dimensions:
    27.9x20.3x12.7cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Model Identity System Interface Service Boundaries Applications

Features:

  • PanelView 600 color display
  • Keypad-and-touch operator input
  • 24 V DC DH-485 configuration
2711-B6C3L1 combines PanelView 600 color graphics with ten function keys and 128 application-defined touch cells. The B input code identifies the combined keypad and touch-screen format.

The catalog communication option is DH-485, while the L1 suffix identifies 24 V DC input power. Both elements must match the installed terminal because another PanelView 600 code can use a different network or power source.

The terminal includes a memory-card slot for stored applications, COMM and FAULT indicators, and a separate RS-232 printer/file-transfer port. On a DH-485 terminal, that RS-232 port is used for printing rather than computer file transfer.

For Allen-Bradley 2711-B6C3L1 PanelView enquiries, Apter Power can help review the DH-485 connection, 24 V DC power variant and installed application.
Allen Bradley 2711-B6C3L1 PanelView Standard 600 Color Keypad and Touch Terminal Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • 2711-B6C3L1: PanelView 600 color operator terminal
  • Combined keypad and touch-screen input
  • Catalog communication option: DH-485
  • L1 suffix: 24 V DC input power
  • 2711-B6C3L1: The DH-485 port connects to an SLC or MicroLogix controller or a DH-485 network
  • The DH-485 programming connector supports application transfer through the documented interface converter
  • A separate RS-232 port supports serial printer connection on this DH-485 terminal
  • COMM and FAULT indicators show communication activity and terminal fault status
  • 2711-B6C3L1: Do not use the terminal as the only emergency-stop or safety-critical operator device
  • Keep personnel- and equipment-safety controls on separate hardwired circuits
  • Match both the DH-485 communication option and L1 DC-power suffix before exchange
  • Use the documented DH-485 programming path; the printer port is not the application-transfer path
  • 2711-B6C3L1: Local color status and control screens for an installed DH-485 system
  • Operator commands through physical keys and application-defined touch objects
  • Numeric and ASCII data entry from the keypad into the terminal application
  • Application storage by memory card and documented serial printing
Description
2711-B6C3L1 combines a 5-inch color display with keypad and touch input while using a direct DH-485 controller connection and the L1 24 V DC power configuration.

2711-B6C3L1 provides a separate RS-232 printer port, but application upload and download remain on the DH-485 communication path. Keeping those port roles distinct prevents a printer connection from being mistaken for the controller or application-transfer route.

2711-B6C3L1 therefore has two configuration boundaries that matter during service: its DH-485 connector and its DC supply. Matching both before a shutdown helps avoid staging an AC or RS-232-based PanelView 600 that cannot restore the installed wiring.
Revisions

Revision Part #

Also known as

2711-B6C3L1 Ser A
2711-B6C3L1/A, Series A, Rev A
2711-B6C3L1 Ser B
2711-B6C3L1/B, Series B, Rev B
2711-B6C3L1 Ser C
2711-B6C3L1/C, Series C, Rev C
2711-B6C3L1X
2711-B6C3L1/X, Series X, Rev X
Alternative Names
2711B6C3L1 27II-B6C3LI 27IIB6C3LI 2711-86C3L1 271186C3L1 2711-B5A16 2711-B6C9 2711-B6C8L1
Technical notes
2711-B6C3L1 uses a DH-485 controller port and a separate RS-232 printer port; the printer port is not the application-transfer path. Upload or download through the DH-485 communication connection, and keep the L1 24 V DC supply boundary intact when servicing or staging a spare.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can a technician upload an application through the RS-232 printer port on 2711-B6C3L1?
No. On this DH-485 configuration, application upload and download use the communication port; the separate RS-232 port is for printing.
Can 2711-B6C3L1 replace an RS-232 (DH-485) PanelView 600 without changing the cable path?
No. Both may use the DH-485 protocol, but this unit has a direct DH-485 controller connector rather than an RS-232 physical interface. Match the installed connector before purchase.
What power source should an electrician prepare for 2711-B6C3L1?
Use the specified 24 V DC installation. The L1 suffix marks the DC-powered configuration, so an AC feed is a stop condition rather than an acceptable substitute.
If printing works but the controller is offline on 2711-B6C3L1, is the DH-485 link proven healthy?
No. The printer uses a separate RS-232 port. Diagnose the DH-485 cabling, network settings and application path independently.
What operator-input test is needed before a repaired 2711-B6C3L1 returns to service?
Exercise both physical keys and touch cells in the restored application. Passing only one input method does not demonstrate the combined B-terminal interface is ready.
Can an AC-powered PanelView 600 be staged as a drop-in spare for 2711-B6C3L1?
No. The L1 suffix makes DC power part of the exact configuration; changing the supply architecture requires an engineered modification, not a direct exchange.