Features:
- DC distribution hub: Routes 125 V DC from the PD core to control, I/O, protection and field-terminal power branches.
- Branch control: Uses individual core switches so downstream cabinet sections can be isolated according to the installed power drawing.
- AC distribution: Provides dedicated routes for ignition-transformer power and supported auxiliary or conversion sources.
TCPS feeds for the I/O cores and Control Engine originate at dedicated TCPD connectors, keeping the principal 125 V DC branches identifiable in the cabinet.
TCEA, DTBC, DTBD and DTBA loads use separate distribution paths, allowing protective, solenoid and wetted-contact functions to be traced to their assigned branch.
The JZ interface group separates standard ignition power, AC-to-DC conversion and optional auxiliary-source arrangements instead of treating them as one interchangeable input.
For General Electric DS200TCPDG2B Power Distribution Module, Apter Power supports document review, quotation and revision-matching requests.
General Electric DS200TCPDG2B Power Distribution Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included unless listed in the stock description. All prices are shown in USD.
- TCPS feeds: J1R, J1S, J1T, J1C and J1D distribute 125 V DC to the power-supply boards serving the assigned control and I/O cores.
- Protective-core feeds: The J7 connector group distributes 125 V DC to TCTG and the three TCEA board locations in the protective core.
- Solenoid-output feeds: J8A through J8D supply the DTBC and DTBD terminal boards used for solenoid output power.
- Wetted-input feeds: J12A and J12B supply DTBA branches used for wetted contact-input interrogation.
- AC conversion input: JZ2 carries incoming AC from terminal board TB1 toward the DACA AC-to-DC converter.
- Reduced-voltage option: JZ3 provides an alternate JZ2 path for the special contact-output 18 circuit when that cabinet configuration is used.
- Auxiliary-source input: JZ4 accepts an isolated UPS or switched backup source and is typically associated with a Black Start Inverter arrangement.
- Ignition-transformer source: JZ5 is the standard AC connection used for ignition-transformer power distribution.
- Ground-reference selection: BJS determines whether the board provides the 125 V DC ground reference or the system uses an external reference point.
- Battery-system convention: GE identifies an ungrounded 125 V DC battery system as standard practice, with BJS retained in the documented position for that arrangement.
- Hardware-defined behavior: TCPD has no software configuration, so jumper state, switch assignment and cabinet wiring define the active distribution setup.
- Power-output monitoring: JPD supplies CTBA for AC and DC output monitoring, linking the distribution board to the cabinet's power-status path.
- Control and I/O core supply: Distributes 125 V DC to TCPS boards serving the Control Engine and associated I/O cores.
- Protective-system supply: Feeds TCTG and TCEA hardware assigned to the Mark V LM protective core.
- Field-terminal power: Supplies DTBC and DTBD solenoid outputs plus DTBA wetted contact-input branches.
- Ignition and auxiliary AC: Routes standard ignition-transformer power and documented backup or conversion sources through separate JZ interfaces.