Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail info@apterpower.com

T9193

/ 4.9
1001 reviews | Need a Specific Revision?
T9193 is an AADvance safety controller certified for SIL 2 and SIL 3, supporting redundant 24V DC power, multiple I/O modules, and fault-tolerant architectures (1oo1D, 1oo2D, 2oo3D).
In Stock
Ships by Saturday, October 17
Fast Shipping Available
Get a quick price for T9193
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for T9193

  • Manufacturer:
    ICS Triplex
  • Part Number:
    T9193
  • Product Family:
    AADvance Controller
  • Product Type:
    Blanking Covers Module
  • Stock:
    1
  • Safety Architectures:
    1oo1D, 1oo2D, 2oo3D
  • Processor Modules Supported:
    3 (max)
  • I/O Modules Supported:
    48 (8 or 16 channels each)
  • Supply Voltage:
    Redundant 24V DC nominal (18-32V range)
  • Channel Isolation:
    ±1.5 kVdc withstand for 1 minute
  • Digital Input Accuracy:
    1.0 Vdc
  • Analog Input Accuracy:
    200 μA
  • Operating Temp (Hazardous - Processor):
    -25°C to +60°C
  • Storage Temperature:
    -40°C to +70°C
  • Humidity:
    10% to 95% RH non-condensing
  • Weight:
    0.5 kg
  • Estimated shipping dimensions:
    17x11x3cm
  • Tariff Code:
    8517795000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Application Communication Safety & Compliance

Features:

  • T9193 provides SIL 2/SIL 3 safety certification with 1oo1D, 1oo2D, and 2oo3D fault-tolerant architectures.
  • Supports 48 I/O modules including digital, analog input, digital output, and analog output types.
  • Redundant 24V DC power with ±1.5 kV isolation; operates -25°C to +70°C with conformal coating.
The T9193 AADvance controller is purpose-built for functional safety applications requiring certification to IEC 61508. Depending on the processor and I/O module configuration, the system achieves SIL 2 or SIL 3 integrity levels. The controller supports three distinct safety architectures: 1oo1D (one-out-of-one with diagnostics) for fail-safe applications; 1oo2D (one-out-of-two with diagnostics) for dual fault-tolerant configurations where a single failure does not cause loss of safety function; and 2oo3D (two-out-of-three with diagnostics) for triple fault-tolerant architectures requiring maximum availability.

The T9193 controller supports up to 48 I/O modules, each available in 8 or 16 channel configurations. Compatible modules include the T9401/T9402 24V DC digital input modules, T9431/T9432 analog input modules, T9451 digital output modules, and T9481/T9482 analog output modules. The controller delivers deterministic scan performance: digital input modules scan in 0.924 ms (simplex), 1.676 ms (dual), or 2.453 ms (triple); analog input modules scan in 1.170 ms (simplex), 1.965 ms (dual), or 2.656 ms (triple); digital output modules scan in 1.174 ms (simplex) or 2.202 ms (dual); analog output modules scan in 0.981 ms (simplex) or 1.761 ms (dual).

The T9193 AADvance controller is engineered for deployment in harsh industrial and hazardous environments. All AADvance modules—including processors, I/O modules, termination assemblies, and backplanes—receive conformal coating during manufacture. This coating meets US MIL-I-46058C and IPC-CC-830 standards, is UL approved, and provides protection against moisture, dust, and chemical contaminants. For hazardous area installations, the T9193 is certified for Class I Division 2 Groups A, B, C, and D locations.

The T9193 ICS TRIPLEX Blanking Covers Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).

ICS TRIPLEX T9193 Blanking Covers Module Manuals, Datasheets, Drivers, Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ICS TRIPLEX T9193 Blanking Covers Module Specs

General

  • Manufacturer ICS TRIPLEX
  • Model T9193
  • Condition New Original ready stock
  • Product Family T9083U,T9082D,T9083D,T9084U
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Oil & Gas (Upstream/Downstream): Offshore drilling platforms, gas processing plants, and Emergency Shutdown (ESD) systems where spare capacity is reserved for future expansion.
  • Petrochemical & Chemical Refining: Critical reaction loop cabinets and safety instrumented systems (SIS) that control safety-critical valves and interlocks.
  • Power Generation: Nuclear and thermal power plants within Boiler Management Systems (BMS) and turbine overspeed protection networks.
  • Critical Infrastructure: Compressors, LNG trains, and large air separation plants where unexpected downtime carries massive economic or safety risks.
  • Slot Connectivity: It plugs seamlessly into T9300 series I/O Base Units (Backplanes). It is secured using an integrated heavy-duty mechanical latch that resists extreme vibrations up to standard industrial ratings, preventing mechanical loosening.
  • Backplane Signal Shielding: The AADvance system relies on high-speed internal buses (using the Secure Network Control Protocol - SNCP) running across the base unit. An empty, exposed slot acts as an antenna for Electrostatic Discharge (ESD) and Electromagnetic Interference (EMI).
  • Galvanic Protection: It acts as a non-conductive cover over the un-mated backplane pins, ensuring no accidental short circuits can occur from dropped screws, metallic dust, or moisture.
  • Preventing Spurious Trips: High-density AADvance I/O modules generate significant localized heat. If a slot is left uncovered, the internal cabinet forced airflow will shortcut through the path of least resistance (the empty slot), starving adjacent running modules of cool air.
  • SIL 2 / SIL 3 Audit Compliance: According to the official AADvance Safety Manual, using genuine blanking covers (like the T9193) on all unpopulated positions is an explicit requirement to maintain the hardware fault tolerance and enclosure ingress protection (IP) ratings during regulatory safety audits.
  • Flame Retardancy: Constructed from premium, halogen-free UL 94-V0 rated flame-retardant engineered plastics (or reinforced anodized aluminum in ruggedized variants) that do not support combustion or release toxic fumes under extreme heat.
Description
The T9193 AADvance controller is a flexible safety system designed for emergency shutdown, fire and gas detection, burner management, and critical process control. This controller supports simplex, dual, and triple modular redundancy configurations, allowing users to select the appropriate fault tolerance level for each application. 

The T9193 supports up to 48 I/O modules (8 or 16 channels each), including digital input (T9401/2), analog input (T9431/2), digital output (T9451), and analog output (T9481/2) modules. Typical scan times for the T9193 include 0.924 ms for simplex digital input, 1.170 ms for simplex analog input, and 1.174 ms for simplex digital output. 

The T9193 offers multiple safety architectures: 1oo1D (fail-safe), 1oo2D (dual fault-tolerant), and 2oo3D (triple fault-tolerant) depending on the processor and I/O module configuration. Sequence of event resolution is 1 ms for processor internal variables and 10 ms for digital input modules. 

The T9193 supports Ethernet and serial ports configurable for Modbus TCP/UDP, CIP, and SNTP protocols. The system uses a secure network communications protocol (SNCP) for distributed control and safety. All AADvance modules feature conformal coating meeting US MIL-I-46058C and IPC-CC-830 standards, and are UL approved for hazardous locations (Class I Div 2 Groups A,B,C,D). 
Alternative Names
T9083U T9082D T9I93 T9083D T9084U T9090M T9100 T9110
Technical notes
The T9193 AADvance controller is certified for SIL 2/SIL 3 safety applications with 1oo1D, 1oo2D, and 2oo3D architectures. Supports 48 I/O modules, redundant 24V DC power, and ±1.5 kV isolation. Scan times: 0.924 ms (DI), 1.170 ms (AI). Operates from -25°C to +70°C. Conformal coated per MIL-I-46058C. Suitable for ESD, F&G, and burner management.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What safety certifications does T9193 hold?
T9193 is certified to IEC 61508 for SIL 2 and SIL 3 safety systems, approved by independent certifying bodies for functional safety control installations.
How many I/O modules can T9193 support?
T9193 supports up to 48 I/O modules including digital (T9401/2), analog input (T9431/2), digital output (T9451), and analog output (T9481/2).
What fault-tolerant architectures does T9193 offer?
T9193 supports 1oo1D (fail-safe), 1oo2D (dual fault-tolerant), and 2oo3D (triple fault-tolerant) configurations for processors and I/O modules.
What is the operating temperature range for T9193?
T9193 processor modules operate from -25°C to +60°C in hazardous environments; I/O modules operate from -25°C to +70°C.

You May Also Like