T9801

/ 4.9
1001 reviews | Need a Specific Revision?
The ICS Triplex T9801 is a 16-channel simplex termination assembly designed for the AADvance safety controller platform, enabling secure and reliable field wiring termination for digital input modules in safety-critical applications.
Get a quick price for T9801
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for T9801

  • Manufacturer:
    ICS Triplex
  • Part Number:
    T9801
  • Product Family:
    AADvance Controller
  • Product Type:
    Digital Input Termination Assembly
  • Number of Channels:
    16
  • Commoning:
    Commoned
  • Backplane Voltage Range:
    18 – 32 Vdc
  • Backplane Current Draw:
    6.5 mA (max)
  • Field Wiring Gauge:
    16 AWG (recommended)
  • Wire Stripping Length:
    6 mm (1/4 in)
  • Terminal Screw Torque:
    0.5 Nm (0.37 ft-lb)
  • Fuse Type (per channel):
    50 mA time-lag, 125 V (Littlefuse 396/TE or equivalent)
  • Fuse Replacement Part:
    T9901 (pack of 20)
  • Compatible Base Unit:
    T9300 I/O Base Unit
  • Operating Temperature (Hazardous):
    -25°C to +60°C (-13°F to +140°F)
  • Operating Temperature (Non-hazardous):
    -25°C to +70°C (-13°F to +158°F)
  • Storage Temperature:
    -40°C to +70°C (-40°F to +158°F)
  • Humidity:
    10% to 95% RH, non-condensing
  • Weight:
    0.1 kg
  • Estimated shipping dimensions:
    13x4x4.5cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Firmware & Updates Monitoring & Control Applications

Features:

  • Mechanical Coding Prevents Mismating
  • Per-Channel Fusing for Field Protection
  • Hazardous Area Ready (Class I, Div 2 / ATEX Zone 2)
The ICS Triplex T9801 is equipped with factory-assigned coding pegs (positions 2, 1, 1) that align exclusively with digital input modules such as the T9401 and T9402. This polarization mechanism physically prevents the insertion of incorrect module types (e.g., analogue or output modules), eliminating a common source of installation error and reducing system downtime.

Each of the 16 channels on the ICS Triplex T9801 includes a 50 mA time-lag fuse (replaceable via T9901), providing localized overcurrent protection for field wiring loops. This design ensures that a single-channel fault does not cascade to adjacent channels or the backplane, maintaining operational continuity for the remaining 15 channels while troubleshooting occurs.

The ICS Triplex T9801 is certified for installation in Class I, Division 2, Groups A, B, C, D hazardous locations and holds ATEX/IECEx certification (Ex ec IIC T4 Gc). When mounted inside an IP54 tool-accessible enclosure, it operates reliably in environments with flammable gases or vapors, making it ideal for oil & gas platforms, refineries, and chemical plants.

The T9801 ICS Triplex Digital Input Termination Assembly, Simplex may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
ICS Triplex T9801 Digital Input Termination Assembly, Simplex Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ICS Triplex T9801 Digital Input Termination Assembly, Simplex

General

  • Manufacturer ICS Triplex
  • Model T9801
  • Condition New Original ready stock
  • Product Family T9802,T9803,T9831
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • No Onboard Firmware – Passive Design:The ICS Triplex T9801 contains no microprocessor, memory, or firmware. Therefore, it never requires firmware updates or security patches, eliminating a common lifecycle management burden for safety systems. All intelligent functions reside in the mated T9401/T9402 input module.
  • ControlFLASH Not Applicable:Unlike processor modules (e.g., T9110), the ICS Triplex T9801 is not programmable and does not appear in RSLinx or ControlFLASH device trees. Its replacement is purely mechanical/electrical — no configuration download is needed after installation.
  • Compatible with AADvance Workbench 1.x, 2.x, and Trusted SIS Workstation:Although the ICS Triplex T9801 itself has no firmware, it is fully compatible with all AADvance software releases (1.x, 2.x, and AADvance-Trusted SIS Workstation). The I/O configuration editor in these software tools recognizes the T9801 when paired with a T9401/T9402 module during hardware mapping.
  • No Version Tracking Required:Because the ICS Triplex T9801 lacks firmware, there are no revision compatibility issues between the termination assembly and the controller. Stock management is simplified — any T9801 unit works with any AADvance digital input module of the correct type, regardless of production date.
  • Channel Status via I/O Module LEDs:The ICS Triplex T9801 does not have onboard indicators. Instead, the mated digital input module (T9401/T9402) provides front-panel LEDs per channel: GREEN (input ON), OFF (input OFF), AMBER (field wiring fault), or RED (channel fault). Operators can quickly localize a problem to a specific field loop without opening the enclosure.
  • Diagnostic Variables in AADvance Workbench:Using the ICS Triplex T9801 within a configured I/O channel, the AADvance Workbench software exposes diagnostic variables such as “Channel Fault,” “Field Fault,” and “No Load.” These variables can be mapped to operator workstations or logged for predictive maintenance — e.g., tracking intermittent open circuits in field wiring.
  • Line Monitoring for Open/Short Detection:When external resistors (R1=15kΩ, R2=3k9) are added to the field loop, the ICS Triplex T9801 enables the T9401/T9402 module to distinguish between four states: Open Circuit, OFF (nominal 8V), ON (nominal 16V), and Short Circuit. This enhanced diagnostics capability is essential for ESD systems where wiring integrity must be continuously verified.
  • Backplane Current Monitoring:The ICS Triplex T9801 draws only 6.5 mA from the T9300 backplane, contributing minimally to system power load. However, the AADvance system’s health variable “System Power Status” can indirectly reflect issues with the backplane supply (18-32 Vdc range) that would affect the T9801 and all termination assemblies on the same I/O bus.
  • Emergency Shutdown (ESD) Systems:The ICS Triplex T9801 terminates field wiring from emergency stop pushbuttons, pressure switches, and solenoid status contacts. In a de-energize-to-trip configuration, it ensures that loss of field power drives the process to a safe state, meeting IEC 61511 requirements for high-integrity shutdowns.
  • Fire & Gas (F&G) Detection Systems:When paired with volt-free contacts from flame detectors, gas sensors, or manual call points, the ICS Triplex T9801 provides reliable signal termination for fire alarm logic. The per-channel 50 mA fuse prevents wiring shorts from disabling an entire zone, preserving system availability during fire events.
  • Burner Management Systems (BMS):In boiler and furnace control, the ICS Triplex T9801 connects limit switches, flame safeguard relays, and purge proof switches. Its hazardous area certification (Class I Div 2) allows direct installation near combustion equipment when housed in an appropriate IP54 enclosure.
  • Pipeline & Remote Valve Monitoring:For remote valve position feedback (open/closed limit switches), the ICS Triplex T9801 offers a compact 16-channel termination solution that reduces panel wiring complexity. Its -40°C to +70°C storage range supports outdoor skid-mounted installations in extreme climates.
Description
The ICS Triplex T9801 serves as the dedicated termination assembly for digital input modules within the Rockwell Automation AADvance safety system. Engineered for simplex (1oo1) architectures, this 16-channel unit provides the physical interface between field devices—such as emergency stop pushbuttons, pressure switches, and flame detectors—and the corresponding digital input modules (T9401/T9402). Its role is mission-critical in Safety Instrumented Functions (SIF), ensuring that field signals are accurately transmitted to the logic solver for processing.

Certified for use in both hazardous (Class I, Division 2) and non-hazardous environments, the ICS Triplex T9801 incorporates coding pegs to prevent mismating with incompatible I/O modules—a key feature for maintaining system integrity. Each channel is protected by a 50 mA time-lag fuse (T9901), offering robust overcurrent protection while allowing easy field replacement. The assembly mounts directly onto the T9300 I/O base unit and accepts 16 AWG field wiring via industry-standard screw terminals, with a recommended torque of 0.5 Nm.

As part of the globally recognized ICS Triplex portfolio—now under Rockwell Automation—the ICS Triplex T9801 is built to meet IEC 61508 SIL 2/SIL 3 requirements when configured within a certified AADvance system. Its straightforward design reduces installation errors, simplifies maintenance, and ensures high availability for emergency shutdown (ESD) and fire & gas (F&G) applications.
Alternative Names
T98O1 T980I T9802 T9803 T9831 T9832 T9833 T9851 T9852
Technical notes
The ICS Triplex T9801 is a passive termination assembly—it does not perform logic processing or communication; its sole function is secure field signal termination. When deploying the ICS Triplex T9801, ensure it is paired with a T9401 or T9402 digital input module and a T9300 I/O base unit; incorrect mating is mechanically prevented by factory-assigned coding pegs (Key A=2, Key B=1, Key C=1).
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What is the exact function of the ICS Triplex T9801 in an AADvance system?
The ICS Triplex T9801 is a simplex termination assembly (TA) that serves as the physical wiring interface between field devices (e.g., switches, sensors) and digital input modules (T9401/T9402). It does not process logic or communicate over the backplane—its role is to terminate field wires, provide overcurrent protection via per-channel fuses, and ensure correct mating with matching I/O modules via coding pegs.
Can the ICS Triplex T9801 be used with analogue input modules?
No. The ICS Triplex T9801 is mechanically coded (Key A=2, Key B=1, Key C=1) to accept only digital input modules such as T9401 (8-channel) or T9402 (16-channel). Attempting to install an analogue input module (e.g., T9431/T9432) is physically prevented by the coding peg system, avoiding wiring errors and potential damage.
What is the field wiring specification for the ICS Triplex T9801?
The ICS Triplex T9801 accepts 16 AWG stranded or solid copper wire with a minimum conductor temperature rating of 85°C. The stripping length is 6 mm (1/4 in), and terminal screw torque must be 0.5 Nm (0.37 ft-lb). For hazardous area installations, the field power supply must be fused externally with a 5A/125V slow-blow fuse unless a Class 2 power source is used.
Can the ICS Triplex T9801 be used in a SIL 3 application?
Yes. When the ICS Triplex T9801 is mated with a T9401 or T9402 digital input module and configured within an AADvance controller with dual or triple processor modules, the overall system can achieve IEC 61508 SIL 3 certification for low-demand and high-demand safety functions. However, the T9801 itself is a simplex assembly; for SIL 3 input functions requiring fault tolerance, use dual (T9802) or triple (T9803) termination assemblies.
What is the maximum backplane current drawn by the ICS Triplex T9801?
The ICS Triplex T9801 draws a maximum of 6.5 mA from the T9300 I/O base unit backplane at 18-32 Vdc. This figure is critical for system power budgeting and heat dissipation calculations. The overall system power consumption should be estimated using the module power tables provided in the AADvance technical manual (e.g., 4.0 W for a T9402 module, plus the T9801’s negligible draw).