Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power provides 6ES7431-7KF00-0AB0 quotations, manuals, product selection, and exact-model matching.

6ES7431-7KF00-0AB0

/ 4.9
1001 reviews | Need a Specific Revision?
Eight field voltage, current or thermocouple signals are converted for an S7-400 controller by Siemens 6ES7431-7KF00-0AB0, an isolated SM 431 analog input module.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for 6ES7431-7KF00-0AB0
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 6ES7431-7KF00-0AB0

  • Manufacturer:
    Siemens
  • Part Number:
    6ES7431-7KF00-0AB0
  • Product Family:
    Siemens Simatic S7-400
  • Product Type:
    SIMATIC S7-400 SM 431 8-Channel Analog Input Module
  • Stock:
    1
  • Analog Input Channels:
    8
  • Supported Measurements:
    Voltage, current and thermocouple
  • Maximum Resolution:
    16 bit including sign
  • Basic Conversion Time:
    10, 16.7, 20 or 100 ms per channel
  • Integration Time:
    2.5, 16.7, 20 or 100 ms
  • Interference Suppression:
    400, 60, 50 or 10 Hz
  • Thermocouple Types:
    B, E, J, K, L, N, R, S, T and U
  • Current Ranges:
    0–20, 4–20, ±3.2, ±5, ±10 and ±20 mA
  • Voltage Ranges:
    1–5 V, ±1 V, ±2.5 V, ±5 V, ±10 V and millivolt ranges
  • Temperature Compensation:
    Internal, external socket or dynamic reference value
  • Shielded Cable Length:
    200 m maximum
  • Voltage Basic Error at 25 °C:
    ±0.1% of input range
  • Current Basic Error at 25 °C:
    ±0.17% of input range
  • Diagnostic Functions:
    Parameterizable diagnostic, limit-value and hardware alarms
  • Channel Isolation:
    Between channels and between channels and backplane bus
  • Isolation Test Voltage:
    1500 V DC
  • Backplane Current at 5 V DC:
    1200 mA maximum
  • Typical Power Loss:
    4.6 W
  • Weight:
    1.433 lbs (0.65 kg)
  • Estimated shipping dimensions:
    2.5x29x21cm
  • Tariff Code:
    85389091
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Input Ranges Temperature Path Conversion Timing Alarms and Isolation

Features:

  • Eight isolated analog channels accept voltage, current or thermocouple signals.
  • Selectable integration relates conversion time to interference-frequency suppression.
  • Diagnostic, hardware and limit-value alarms report configured channel conditions.
The SM 431 converts field measurements into signed S7-400 process values instead of passing raw sensor levels to the CPU.

Thermocouple channels combine characteristic linearization with an internal, external or dynamic reference-temperature path.

Channel-to-channel and backplane isolation separate the measurement points from the rack communication circuit.

The Siemens 6ES7431-7KF00-0AB0 S7-400 SM 431 Analog Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7431-7KF00-0AB0 S7-400 SM 431 Analog Input Module Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Assigning a measuring method to each channel

  • Voltage paths: Each selected voltage range defines the electrical span converted into the channel word.
  • Current paths: Current transmitters use the configured bipolar, 0–20 mA or 4–20 mA range.
  • Thermocouple paths: Supported thermocouple types are linearized after their measured voltage is acquired.
  • Range protection: The documented destruction limits apply to the physical input before software scaling.

Turning thermocouple voltage into temperature data

  • Cold junction: The reference temperature can come from the internal sensor, an external compensation socket or a dynamic value.
  • Linearization: The selected thermocouple curve converts the compensated millivolt signal into a temperature result.
  • Channel assignment: Thermocouple type and compensation method are configured for the channel that receives the sensor.
  • Wiring reach: Shielded field cable remains within the documented maximum path length.

Balancing channel update and mains rejection

  • Integration setting: The configured integration interval sets the corresponding interference-suppression frequency.
  • Update interval: A shorter basic conversion time refreshes a channel sooner than the longer rejection settings.
  • Resolution: The converted channel value uses as many as sixteen bits including its sign.
  • Engineering choice: Timing is selected from the required update rate and the dominant interference frequency.

Separating measurement status from rack communication

  • Diagnostic alarm: A parameterized module or input condition can request a diagnostic interrupt.
  • Limit alarm: Configured upper or lower boundaries can produce a limit-value event.
  • Hardware interrupt: The controller receives the enabled process event through the backplane.
  • Electrical separation: Channels are isolated from each other and from the S7-400 bus circuit.
Description
Siemens 6ES7431-7KF00-0AB0 is the SIMATIC S7-400 SM 431 analog input module that acquires eight voltage, current or thermocouple signals for the controller. Its input circuitry converts each field value into a signed digital word while keeping the channels isolated from one another and from the rack backplane.

Range selection on 6ES7431-7KF00-0AB0 determines how an incoming electrical level is interpreted before conversion. Voltage and current transmitters use their assigned input ranges, whereas thermocouples pass through characteristic linearization and the selected cold-junction compensation path before the CPU receives a temperature value.

For noise rejection, the integration setting of 6ES7431-7KF00-0AB0 links the conversion interval to the interference frequency that must be suppressed. A faster channel update uses the shorter conversion choice, while longer integration is available when 50 or 60 Hz rejection governs the measurement path.

Diagnostic and limit-value events from 6ES7431-7KF00-0AB0 are transferred through the S7-400 backplane as parameterized alarms. These messages let the program distinguish an out-of-range or module condition from the ordinary analog value without combining that status with the field measurement itself.
Alternative Names
6ES74317KF000AB0 6ES7 431-7KF00-0AB0 6ES7431 7KF00 0AB0 Siemens 6ES7431-7KF00-0AB0 SM 431 6ES7431-7KF00-0AB0 S7-400 8AI 6ES7431-7KF00-0AB0 6ES7431-7KFOO-0AB0 6ES743I-7KF00-0AB0
Technical notes
Siemens 6ES7431-7KF00-0AB0 accepts eight voltage, current or thermocouple channels and applies a separately selected measuring range to each point. Cold-junction compensation must match the installed thermocouple wiring.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which sensor types can be wired directly to 6ES7431-7KF00-0AB0?
Use the 6ES7431-7KF00-0AB0 with a configured voltage, current or supported thermocouple signal and the matching input range.
How should mains interference be reduced on 6ES7431-7KF00-0AB0?
Select the 6ES7431-7KF00-0AB0 integration time that corresponds to the documented 50 Hz or 60 Hz suppression setting and use shielded wiring.
Why can a thermocouple value from 6ES7431-7KF00-0AB0 be offset?
Check that the thermocouple type and cold-junction method configured for 6ES7431-7KF00-0AB0 match the actual sensor and compensation wiring.
Does one faulty input remove isolation from the other 6ES7431-7KF00-0AB0 channels?
No. The analog inputs of 6ES7431-7KF00-0AB0 are isolated from one another and from the backplane bus.
What should be reviewed when 6ES7431-7KF00-0AB0 reports a limit alarm?
Compare the 6ES7431-7KF00-0AB0 channel value with its configured upper and lower limits before checking whether the event is a diagnostic alarm.
Can a four-wire current transmitter connect to 6ES7431-7KF00-0AB0?
Yes. A 6ES7431-7KF00-0AB0 current channel supports the documented four-wire transducer connection when its measuring range is configured correctly.