Features:
- Delivers 40 W of RX3i backplane power from AC or DC mains.
- The nominal input accepts 120/240 VAC or 125 VDC across its supported wide input range.
- Fault, overload, and overtemperature LEDs provide local service feedback; this model does not participate in load sharing or redundancy.
The nominal input accepts 120/240 VAC or 125 VDC across its supported wide input range.
Fault, overload, and overtemperature LEDs provide local service feedback; this model does not participate in load sharing or redundancy.
IC695PSA040 occupies the RX3i power-supply position and provides separate backplane rails within its 40 W total output budget.
General Electric IC695PSA040 PACSystems RX3i 40 W AC/DC Power Supply is available for Apter Power quotation and official-documentation support.
General Electric IC695PSA040 PACSystems RX3i 40 W AC/DC Power Supply Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
IC695PSA040 Source Connection
- Input selection: Wire the supply for the supported 120/240 VAC or 125 VDC source and verify the actual terminal voltage.
- Neutral scheme: Use the required RX3i floating-neutral connection when the AC source is not referenced to ground.
- Conductor range: Use one 14 to 22 AWG conductor per terminal and the specified protective device.
- Disconnect: Open the upstream energy-isolating device before changing line, neutral, or DC polarity wiring.
IC695PSA040 Rail Allocation
- Total limit: The combined backplane demand must remain within the 40 W supply rating after derating.
- Low-voltage rails: Check the 3.3 VDC and 5 VDC loads separately; each has its own maximum contribution.
- Relay rail: Include the 24 VDC relay load rather than treating it as external field power.
- Architecture limit: PSA040 cannot share load or provide a redundant supply path with another unit.
IC695PSA040 Service Checks
- LEDs: Power, P/S Fault, Overload, Overtemperature
- Load Sharing and Redundancy: Not supported
- Operating Temperature: 0 to 60 °C
- Humidity: 5% to 95%, non-condensing
IC695PSA040 Installation Practice
- Backplane: Seat IC695PSA040 only in a supported RX3i Universal Backplane power-supply position.
- Identity: Match the complete catalog and revision before replacement.
- Configuration: Validate the controller hardware configuration before startup.
- Safety: Remove hazardous energy and follow the site installation procedure.