- Universal input architecture accepts several industrial sensor and transmitter types
- Two four-channel groups support project-specific signal assignments
- Dedicated cold-junction inputs support thermocouple compensation arrangements
IC695ALG600 is a General Electric PACSystems RX3i Universal Analog Input Module for mixed process measurements.
The module lets each application combine supported low-level voltage, current-loop, thermocouple, RTD, and resistance measurements within the documented channel and group rules.
Before installation or replacement, verify the complete catalog number, firmware and configuration, terminal assembly, sensor type, channel range, grounding, shielding, CJC arrangement, RTD wiring, and stored scaling values.
Availability, condition, price, and shipping time for IC695ALG600 are confirmed during quotation.
General Electric IC695ALG600 PACSystems RX3i Universal Analog Input Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Thermocouple selections include types B, C, E, J, K, N, R, S, and T
- RTD selections include platinum, nickel, nickel-iron, and copper characteristic curves
- Resistance measurements cover six documented ranges through 4000 Ω
- The eight general-purpose inputs are arranged as two groups of four channels
- Two dedicated CJC inputs support thermocouple terminal-temperature compensation
- Three-wire RTD lead-resistance compensation must be enabled when required by the selected configuration
- Slow hot insertion can delay the Module OK indication for as long as two seconds
- Hot removal can report two Loss of I/O Module faults for one physical removal
- A missing or unlocked terminal block does not generate a Loss of Terminal Block fault on this module family
- Thermocouple temperature acquisition with cold-junction compensation
- RTD temperature and industrial resistance measurement
- Mixed voltage and 0...20 mA or 4...20 mA process-signal acquisition